Before You Begin Installing

151450

3-9

3.6.1.2 Current Draw Worksheet for 5600 ULC

Use to determine amp-hour requirements during alarm/battery standby operation.
(Copy the page if additional space is required.) You can install up to 25 SLC devices
and two 5635 Remote Annunciator. The maximum battery size for ULC installations is
18 Amp/hr.

Table 3-3: Current Calculation Worksheet for SLC Devices for ULC

Device

# of Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this formula: This column X This column = Current per number of
devices.

Fire Panel (Current draw from
battery)

1

Standby: 165 mA

165 mA

Alarm: 220 mA

220 mA

Accessory Modules

5635 Remote Annunicator

2

Standby: 37 mA

mA

Alarm: 40 mA

mA

Addressable SLC Detectors

HFS-PA

25 max.

Standby: .27 mA

Alarm: 6.5 mA

mA

mA

HFS-PTA

mA

mA

HFS-DA

mA

mA

HFS-TA

mA

mA

SK-Photo

mA

mA

SK-Photo-T

mA

mA

SK-DUCT

mA

mA

SK-Heat

mA

mA

Addressable SLC Modules

HFS-MMA

25 max

Standby/Alarm: .375 mA

mA

mA

SK-Pull-SA

Standby/Alarm: .375 mA

mA

mA

SK-PULL-DA

Standby/Alarm: .375 mA

mA

mA

HFS-MRA

Standby/Alarm: .255mA

mA

mA

SK-Minimon

Standby/Alarm: .375 mA

mA

mA

SK-Relay

Standby/Alarm: .375 mA

mA

mA

SK-ISO

10 max

Standby/Alarm: .45 mA

mA

mA

A

Total System Current

Auxiliary Devices

Refer to devices manual for current rating.

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

B

Auxiliary Devices Current

Notification Appliance Circuits

Refer to device manual for current rating.

Alarm: mA

mA

Alarm: mA

mA

Alarm: mA

mA

C

Notification Appliances Current

mA

D

Total current ratings of all devices in system (line A + line B + C)

mA

mA

E

Total current ratings converted to amperes (line D x .001):

A

A