4.9

Notification Appliance/Auxiliary Power Circuits

The two outputs of the 5600 FACP can be programmed to be used as NACs or as
Aux power.

This section of the manual explains how to install conventional notification appliances
and how these terminals can be used for auxiliary power.

4.9.1

Conventional Notification Appliance Circuit

The 5600 supports Class B (Style Y) configurations for notification appliance
applications.

You must use an appliance from the list of compatible appliances in the Appendix A at
the back of this manual. Each circuit can source up to 2.0A (total current for the
system must not exceed 2.0A)

To install a Class B notification appliance circuit:

1. Wire Class B Notification appliances as shown in Figure 4-15.

2. Configure the circuit through programming.

Figure 4-15 Class B Notification Appliance Circuit Wiring