beautypg.com

3 ulc requirements, Ulc requirements – SilentKnight 5600 User Manual

Page 20

background image

Model 5600 Installation and Operation Manual

2-4

151450

2.2.2

Requirements for Central Station Fire Alarm
Systems

1. Use both phone lines. Enable phone line monitors for both lines.

2. You must program a phone number and a test time so that the 5600 sends an

automatic daily test to the central station.

3. The AC Loss Hours option must be set from 1-3 hours.

2.2.3

Requirements for Local Protected Fire Alarm
Systems

At least one UL listed supervised notification appliance must be used.

2.2.4

Requirements for Remote Station Protected Fire
Alarm Systems

1. Do not exceed the current load restrictions shown in Section 3.6.

2. The AC Loss Hours option must be set from 1-3 hours.

2.3

ULC Requirements

Install in accordance with the Canadian Electrical Code, C22.1, Part 1, Section 32.