Model 5600/5600C/5600HV Basic Operating Instructions

These Instructions must be framed and displayed next to the5600 panel in
accordance with NFPA 72 fire code for Local Protected Fire Alarm
Systems. Test the system in accordance to NFPA 72. Refer to Installation
Manual P/N 151450 for more information regarding this control panel.

Operation

Task to Perform

Silence Alarms and
Troubles

Press

. Silence LED will light.

Reset Alarms

Press .

Acknowledge Alarms
and Troubles

Press .

View Alarms

Zones that are in alarm will have their alarm LED on. To view all points
in alarm press Alarm ID followed by

or

button to view the SLC ID

for each point.

View Supervisories

Zones that are in supervisory will have their supervisory LED on. To
view all points in supervisory press Supervs ID followed by

or

button to view the SLC ID for each point.

View Troubles

Zones that are in trouble will have their trouble LED on. To view all
points in trouble press Trouble ID followed by

or

button to view

the SLC ID for each point.

Conduct a Fire Drill

1. Press

to start Fire Drill.

2. Press

to end Fire Drill.

Dialer Test

Press

and

key at same time.

Lamp Test

Press

and

key at same time.

Enable / Disable a Zone
or Circuit

Press the corresponding disable key. Press it again to enable the zone
or circuit. For ULC, you must enter the Installation code after pressing
Zone Enable/Disable.

Remote Connection
Feature (ULC
Installations Only)

Press the

and

at the same time to disconnect the

communication paths to the Central Station and/or remote station. The
PZT on the panel will sound and the General Trouble LED will be
flashing. This will remain active until you press the Walk test and
Acknowledge buttons again.

For Service call:

P/N 53610

Rev. A

ECN 10-157