Model 5600 Installation and Operation Manual

4-8

151450

2. Connect the main control panel battery cables to the battery cable extenders as

shown in Figure 4-6.

Figure 4-6 Splicing Control panel Battery Cable to RBB Battery Cable Extenders

3. Run extended battery cable from control panel cabinet through conduit to RBB

cabinet.
See Figure 4-7.

Figure 4-7 Battery Connections in the RBB Cabinet

Note: Figure 4-7 is an example of how the wire connections can be routed. However, any other cabinet

knock-outs (on either the main control panel or the RBB cabinet), that are not previously being
used may be utilized to connect conduit between the two cabinets.

4. Connect battery leads to the backup battery terminals. See Figure 4-7.

Observe the proper polarity to prevent damage to the batteries or the control
panel.

5. Insert the RBB cover screws into the cover mounting holes (see Figure 4-7).

Screw the cover screw ¾ of the way into the cover mounting hole.

RBB Cabinet
Cover Screws

Conduit

Conduit
Coupler

RBB Cabinet
Cover Screws

+

+

-

-