2.2
COMPLETE solution
The picture above shows a principle layout, it is intended for indicating the presence of the components, not their position, in
the AHU controlled by the EVCO device. It is also NOT intended for indicating the real layout of the AHU.
N.B. 1) The coil electric heater is an alternative to the hot water coil.
2) The CO
2
probe is an optional just in the 3-speed fans version. In this version the heating
regulation function based on the return air temperature is also available.
The following are added to the functions and parts of the COMPACT version:
-
High efficiency Recovery heat exchanger/Heat exchanger
-
Differential pressure switch
-
Electric heaters protection
-
Electric heaters option or Hot water coil option (parameter PG02)
-
Outside air damper option (parameter PG04)
-
Summer By-Pass damper option (parameter PG08)
-
Outdoor Air Temperature Probe
-
Return Air Temperature Probe
-
Supply Air Temperature Probe
-
CO
2
and air quality sensor for automatic fan speed modulation option
-
Heating control based on return temperature probe
Notes
•
The electric heaters can be used instead of (not together with) the how water coil
•
The COMPLETE solution is configured by default for driving 3 speed fans (PG10 = DO)