C-PRO MICRO SAVE APPLICATION MANUAL

Page 30

Code

Parameter description

Default

Min

Max

UM

Menu

Notes

VARIOUS PARAMETERS

PH01

Minimum temperature value

-15.0

-20.0

-4.0

PH02

°C

°F

IS-V

PH02

Maximum temperature value

95.0

PH01

110.0
230.0

°C

°F

IS-V

PH03

Minimum CO

2

probe PPM value

0

0

PH04

ppm

IS-V

PH04

Maximum CO

2

probe PPM value

0

PH03

10000

ppm

IS-V

PH05

Enables unit switch-on/off from
“Start/Stop” digital input

Yes (1)

No (0)

Yes (1)

-

IS-V

PH06

Enables unit switch-on/off from supervisor

No (0)

No (0)

Yes (1)

IS-V

PH18

Cancels the alarms log

NO (0)

NO (0)

YES (1)

-

IS-V

Set YES (1)
ad wait for
the NO (0)
value to be
read again

PH20

Enable buzzer

Yes (1)

No (0)

Yes (1)

-

IS-V

PH30

Temperature unit of measurement
0: °Celsius
1: °Fahrenheit

0 (°C)

0 (°C)

1 (°F)

-

IS-V

PH99

Reset the factory parameters default

NO (0)

NO (0)

YES (1)

-

IS-D

Wait for the
NO (0)
value to be
read again
on reset
completion

PSd2

Installer level password (2)

0

-999

9999

-

IS

Level 3

MANUFACTURER MENU

CONFIGURATION PARAMETERS
After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.

PG01

Enabling of expansion

Yes (1)

No (0)

Yes (1)

-

CO-G

PG02

Selection of type of device for heating:
0: Disabled
1: Hot water coil only
2: Electric heater coil only

Heaters

(2)

Disabled

(0)

Heaters

(2)

-

CO-G

PG03

Type of recovery heat exchanger by-pass
damper control:
0: Digital Control (DO7)
1: Analogue Control (AO3)

DO (0)

DO (0)

AO (1)

-

CO-G

PG04

Outside air damper enabling

Yes (1)

No (0)

Yes (1)

-

CO-G

PG05

Enabling of post-ventilation

Yes (1)

No (0)

Yes (1)

-

CO-G

PG06

Enabling of recovery heat exchanger anti-
freeze protection

Type 1

(1)

Disabled

(0)

Type 2

(2)

-

CO-G

PG08

Enabling of recovery heat exchanger by-pass
in summer

Yes (1)

No (0)

Yes (1)

CO-G

PG09

Activation of outside air damper end run

Yes (1)

No (0)

Yes (1)

CO-G

PG10

Type of fan

DO (0)

DO (0)

AO (1)

-

CO-G

PSd1

User level password (1)

0

-999

9999

-

CO-G

PSd2

Installer level password (2)

0

-999

9999

-

CO-G

PSd3

Manufacturer level password (3)

0

-999

9999

-

CO-G