C-PRO MICRO SAVE APPLICATION MANUAL
Page 29
Code
Parameter description
Default
Min
Max
UM
Menu
Notes
FANS
PF01
Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
3: Automatic with CO
2
sensor
0
0
3
-
IS-F
PF03
Fans speed in COMFORT period
V2
V1
V3
-
IS-F
PF04
Fans speed in ECONOMY period
V1
V0
V2
-
IS-F
PF05
Fans speed in RTC error
V0
V0
V3
-
IS-F
Only if
PF01=1/2 /3
PF12
Fans speed in COMFORT with presence
sensor active
V3
V1
V3
-
IS-F
PF13
Speed in case of « non working » day
V0
V0
V3
-
IS-F
PF14
Set point CO
2
for Speed 1 and 2
500
PH03
PF15
ppm
IS-F
Speed 1:
CO
2
< PF14
Speed 2:
CO
2
≥ PF14
CO
2
< PF15
Speed 3:
CO
2
> PF15
PF15
Set point CO
2
for Speed 2 and 3
1100
PF14
PH04
ppm
IS-F
PF21
Speed variator value corresponding to speed V1
33.50
0.00
100.00
%
IS-F
PF22
Speed variator value corresponding to speed V2
66.50
0.00
100.00
%
IS-F
PF23
Speed variator value corresponding to speed V3
100.00
0.00
100.00
%
IS-F
Only version
with variator
HEATING COILS
This menu is only accessible if PG02>0
Pb01
Regulation probe for heating
0: Supply Probe
1: Return Probe
0
0
1
IS-B
FREECOOLING
Pr04
Outside air/recovery heat exchanger by-
pass temperature set point in summer
15.0
PH01
PH02
°C
°F
IS-FC
Pr05
Return air/recovery heat exchanger by-
pass temperature set point in summer
22.0
PH01
PH02
°C
°F
IS-FC
ALARM PARAMETERS
PA01
Enabling fans working hours alarm
Active
(1)
Not-
active (0)
Active (1)
-
IS-S
PA02
Signals working hours alarms on alarm
relay
No (0)
No (0)
Yes (1)
-
IS-S
PA04
Signals the supply/return fans thermal
overload alarm on the alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA07
Differential pressure switch alarm delay on
unit start-up
60
0
999
sec
IS-S
PA11
Signals the coil anti-freeze alarm on the
alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA15
Signalling of the outside air damper limit
switch alarm on alarm relay
Yes (1)
No (0)
Yes (1)
IS-S
Only if
PG02=1
PA21
Signalling of high/low temperature alarms
on the alarm relay
yes (1)
No (0)
Yes (1)
IS-S
PA23
Signalling of expansion alarm on alarm
relay
Yes (1)
No (0)
Yes (1)
IS-S
PA25
Signals RTC alarm on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA27
Signals probe alarms on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S