FANS

PF01

Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
3: Automatic with CO

2

sensor

0

0

3

-

IS-F

PF03

Fans speed in COMFORT period

V2

V1

V3

-

IS-F

PF04

Fans speed in ECONOMY period

V1

V0

V2

-

IS-F

PF05

Fans speed in RTC error

V0

V0

V3

-

IS-F

Only if
PF01=1/2 /3

PF12

Fans speed in COMFORT with presence
sensor active

V3

V1

V3

-

IS-F

PF13

Speed in case of « non working » day

V0

V0

V3

-

IS-F

PF14

Set point CO

2

for Speed 1 and 2

500

PH03

PF15

ppm

IS-F

Speed 1:
CO

2

< PF14

Speed 2:
CO

2

≥ PF14

CO

2

< PF15

Speed 3:
CO

2

> PF15

PF15

Set point CO

2

for Speed 2 and 3

1100

PF14

PH04

ppm

IS-F

PF21

Speed variator value corresponding to speed V1

33.50

0.00

100.00

%

IS-F

PF22

Speed variator value corresponding to speed V2

66.50

0.00

100.00

%

IS-F

PF23

Speed variator value corresponding to speed V3

100.00

0.00

100.00

%

IS-F

Only version
with variator

HEATING COILS
This menu is only accessible if PG02>0

Pb01

Regulation probe for heating
0: Supply Probe
1: Return Probe

0

0

1

IS-B

FREECOOLING

Pr04

Outside air/recovery heat exchanger by-
pass temperature set point in summer

15.0

PH01

PH02

°C

°F

IS-FC

Pr05

Return air/recovery heat exchanger by-
pass temperature set point in summer

22.0

PH01

PH02

°C

°F

IS-FC

ALARM PARAMETERS

PA01

Enabling fans working hours alarm

Active

(1)

Not-

active (0)

Active (1)

-

IS-S

PA02

Signals working hours alarms on alarm
relay

No (0)

No (0)

Yes (1)

-

IS-S

PA04

Signals the supply/return fans thermal
overload alarm on the alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA07

Differential pressure switch alarm delay on
unit start-up

60

0

999

sec

IS-S

PA11

Signals the coil anti-freeze alarm on the
alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA15

Signalling of the outside air damper limit
switch alarm on alarm relay

Yes (1)

No (0)

Yes (1)

IS-S

Only if
PG02=1

PA21

Signalling of high/low temperature alarms
on the alarm relay

yes (1)

No (0)

Yes (1)

IS-S

PA23

Signalling of expansion alarm on alarm
relay

Yes (1)

No (0)

Yes (1)

IS-S

PA25

Signals RTC alarm on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA27

Signals probe alarms on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S