C-PRO MICRO SAVE APPLICATION MANUAL
Page 26
Code
Parameter description
Default
Min
Max
UM
Menu
Notes
Level 3
MANUFACTURER MENU
CONFIGURATION PARAMETERS
After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.
PG01
Enabling of expansion
No (1)
No (0)
Yes (1)
-
CO-G
PG02
Selection of type of device for heating:
0: Disabled
1: Hot water coil only
2: Electric heater coil only
Disabled
(0)
Disabled
(0)
Heaters
(2)
-
CO-G
PG03
Type of recovery heat exchanger by-pass
damper control:
0: Digital Control (DO7)
1: Analogue Control (AO3)
AO (1)
DO (0)
AO (1)
-
CO-G
PG04
Outside air damper enabling
No (0)
No (0)
Yes (1)
-
CO-G
PG05
Enabling of post-ventilation
No (0)
No (0)
Yes (1)
-
CO-G
PG06
Enabling of recovery heat exchanger anti-
freeze protection
Type 1
(1)
Not-active
(0)
Type 2 (2)
-
CO-G
PG08
Enabling of recovery heat exchanger by-
pass in summer
No (0)
No (0)
Yes (1)
CO-G
PG09
Activation of outside air damper limit switch
No (0)
No (0)
Yes (1)
CO-G
PG10
Type of fan
DO (0)
DO (0)
AO (1)
-
CO-G
PSd1
User level password (1)
0
-999
9999
-
CO-G
PSd2
Installer level password (2)
0
-999
9999
-
CO-G
PSd3
Manufacturer level password (3)
0
-999
9999
-
CO-G
FANS
PF06
Minimum time that must pass for the switch-
on/off of each individual step of the fans
3
0
999
Sec
CO-F
PF07
Temperature setpoint of the fans for anti-
freeze protection of the recovery heat
exchanger
2.0
PH01
PH02
°C
°F
CO-F
PF08
Differential for anti-freeze protection of
the recovery heat exchanger
2.0
0.0
20.0
36.0
°C
°F
CO-F
PF09
Minimum stand-by time before requesting
switch-off of a further fan step
5
1
99
Min
CO-F
PF10
Differential for the by-pass of the recovery
unit damper in anti-freeze protection mode
2.0
0.0
20.0
36.0
°C
°F
CO-F
PF11
Fans working time in post-ventilation
mode
30
0
999
Sec
CO-F
OUTSIDE AIR DAMPER
This menu is only accessible if PG04=1
PS01
Fans switch-on delay from outside air
damper activation
45
0
999
Sec
CO-SE
Reading only
PS02
Outside air damper switch-OFF delay from
fans switch-off
15
0
999
Sec
CO-SE
PS05
Delay of outside air damper end run
60
0
999
Sec
CO-SE
RECOVERY HEAT EXCHANGER
Pr01
Anti-freeze temperature minimum setpoint
1.0
PH01
PH02
°C
°F
CO-RH
Pr02
Anti-freeze temperature minimum
differential
2.0
0.0
20.0
36.0
°C
°F
CO-RH
Pr03
Recovery heat exchanger by-pass cycle
time for cyclical defrosting
5
1
99
Min
CO-RH