C-PRO MICRO SAVE APPLICATION MANUAL

Page 28

5.2 COMPLETE solution list of configuration parameters

Code

Parameter description

Default

Min

Max

UM

Menu

Notes

Level 1

USER MENU

USER

SPHM

Supply temperature heating setpoint

22.0

PH01

PH02

°C

°F

UT

SPHR

Return temperature heating setpoint

20.0

PH01

PH02

°C

°F

UT

PF02

Fans speed in manual regulation mode

V3

V0

V3

UT

Only if
PF01=0
(Manual
Regulation)

PSd1

User level password (1)

0

-999

9999

-

UT

Level 2

INSTALLER MENU

CLOCK

PT01

Start of the COMFORT time period

10:00:00

00:00:00

23:59:59

-

OR

PT02

Start of the ECONOMY time period

16:00:00

00:00:00

23:59:59

-

OR

PT11

Sunday

0

Working

0

Working

1

Not Working

OR

PT12

Monday

0

Working

0

Working

1

Not Working

OR

PT13

Tuesday

0

Working

0

Working

1

Not Working

OR

PT14

Wednesday

0

Working

0

Working

1

Not Working

OR

PT15

Thursday

0

Working

0

Working

1

Not Working

OR

PT16

Friday

0

Working

0

Working

1

Not Working

OR

PT17

Saturday

0

Working

0

Working

1

Not Working

OR

MAINTENANCE

PM01

Functioning hours maximum limit for fans.
The relevant alarm will be triggered over
this limit

8000

0

100000

Hours

IS-MA

PM02

Outlet fan functioning hours

0

0

100000

Hours

IS-MA

PM03

Return fan functioning hours

0

0

100000

Hours

IS-MA

PM90

Last date on which maintenance was
performed on the machine

IS-MA

PM11

Calibration of the anti-freeze air
temperature probe

0.0

-10.0
-18.0

10.0
18.0

°C

°F

IS-MA

PM12

Calibration of the outlet air temperature
probe

0.0

-10.0
-18.0

10.0
18.0

°C

°F

IS-MA

PM13

Calibration of the return air temperature
probe

0.0

-10.0
-18.0

10.0
18.0

°C

°F

IS-MA

PM15

Calibration of the outside air introduction
temperature probe

0.0

-10.0
-18.0

10.0
18.0

°C

°F

IS-MA