C-PRO MICRO SAVE APPLICATION MANUAL

Page 25

Code

Parameter description

Default

Min

Max

UM

Menu

Notes

MAINTENANCE

PM01

Max number of fans working hours. The
relevant alarm occurs over this limit

20000

0

100000

Hours

IS-MA

PM02

Supply fan working hours

0

0

100000

Hours

IS-MA

PM03

Return fan working hours

0

0

100000

Hours

IS-MA

PM90

Last maintenance date

IS-MA

PM11

Anti-freeze air temperature probe offset

0.0
0.0

-10.0
-18.0

10.0
18.0

°C

°F

IS-MA

FANS

PF01

Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor

0

0

2

IS-F

PF03

Fans speed in COMFORT period

V2

V0

V3

IS-F

PF04

Fans speed in ECONOMY period

V1

V0

V3

IS-F

PF05

Fans speed in RTC error

V0

V0

V3

IS-F

Only if
PF01=1/2 /3

PF12

Fans speed in COMFORT with presence
sensor active

V3

V1

V3

IS-F

PF13

Speed in case of « non Working » day

V0

V0

V3

IS-F

PF21

Speed variator value corresponding to speed V1

33.50

0.00

100.00

%

IS-F

PF22

Speed variator value corresponding to speed V2

66.50

0.00

100.00

%

IS-F

PF23

Speed variator value corresponding to speed V3

100.00

0.00

100.00

%

IS-F

Only version
with variator

ALARM PARAMETERS

PA01

Enabling fans working hours alarm

Active

(1)

Not-active

(0)

Active (1)

-

IS-S

PA02

Signals working hours alarms on alarm
relay

No (0)

No (0)

Yes (1)

-

IS-S

PA04

Signals the supply/return fans thermal
overload on the alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA25

Signals RTC alarm on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA27

Signals probe alarms on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

VARIOUS PARAMETERS

PH01

Minimum temperature value

-15.0

-20.0

-4.0

PH02

°C

°F

IS-V

PH02

Maximum temperature value

95.0

PH01

110.0
230.0

°C

°F

IS-V

PH05

Enables unit switch-on/off from
"Start/Stop" digital input

Yes (1)

No (0)

Yes (1)

-

IS-V

PH06

Enables unit switch-on/off from supervisor

No (0)

No (0)

Yes (1)

IS-V

PH18

Cancels the alarms log

NO (0)

NO (0)

YES (1)

-

IS-V

Set Yes (1)
ad wait for
the NO (0)
value to be
read again

PH20

Enable buzzer

Yes (1)

No (0)

Yes (1)

-

IS-V

PH30

Temperature unit of measurement
0: °Celsius
1: °Fahrenheit

0 (°C)

0 (°C)

1 (°F)

-

IS-V

PH99

Reset the factory parameters default

NO (0)

NO (0)

YES (1)

-

IS-D

Wait for the
NO (0)
value to be
read again
on reset
completion

PSd2

Installer level password (2)

0

-999

9999

-

IS