C-PRO MICRO SAVE APPLICATION MANUAL
Page 25
Code
Parameter description
Default
Min
Max
UM
Menu
Notes
MAINTENANCE
PM01
Max number of fans working hours. The
relevant alarm occurs over this limit
20000
0
100000
Hours
IS-MA
PM02
Supply fan working hours
0
0
100000
Hours
IS-MA
PM03
Return fan working hours
0
0
100000
Hours
IS-MA
PM90
Last maintenance date
IS-MA
PM11
Anti-freeze air temperature probe offset
0.0
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
FANS
PF01
Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
0
0
2
IS-F
PF03
Fans speed in COMFORT period
V2
V0
V3
IS-F
PF04
Fans speed in ECONOMY period
V1
V0
V3
IS-F
PF05
Fans speed in RTC error
V0
V0
V3
IS-F
Only if
PF01=1/2 /3
PF12
Fans speed in COMFORT with presence
sensor active
V3
V1
V3
IS-F
PF13
Speed in case of « non Working » day
V0
V0
V3
IS-F
PF21
Speed variator value corresponding to speed V1
33.50
0.00
100.00
%
IS-F
PF22
Speed variator value corresponding to speed V2
66.50
0.00
100.00
%
IS-F
PF23
Speed variator value corresponding to speed V3
100.00
0.00
100.00
%
IS-F
Only version
with variator
ALARM PARAMETERS
PA01
Enabling fans working hours alarm
Active
(1)
Not-active
(0)
Active (1)
-
IS-S
PA02
Signals working hours alarms on alarm
relay
No (0)
No (0)
Yes (1)
-
IS-S
PA04
Signals the supply/return fans thermal
overload on the alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA25
Signals RTC alarm on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA27
Signals probe alarms on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
VARIOUS PARAMETERS
PH01
Minimum temperature value
-15.0
-20.0
-4.0
PH02
°C
°F
IS-V
PH02
Maximum temperature value
95.0
PH01
110.0
230.0
°C
°F
IS-V
PH05
Enables unit switch-on/off from
"Start/Stop" digital input
Yes (1)
No (0)
Yes (1)
-
IS-V
PH06
Enables unit switch-on/off from supervisor
No (0)
No (0)
Yes (1)
IS-V
PH18
Cancels the alarms log
NO (0)
NO (0)
YES (1)
-
IS-V
Set Yes (1)
ad wait for
the NO (0)
value to be
read again
PH20
Enable buzzer
Yes (1)
No (0)
Yes (1)
-
IS-V
PH30
Temperature unit of measurement
0: °Celsius
1: °Fahrenheit
0 (°C)
0 (°C)
1 (°F)
-
IS-V
PH99
Reset the factory parameters default
NO (0)
NO (0)
YES (1)
-
IS-D
Wait for the
NO (0)
value to be
read again
on reset
completion
PSd2
Installer level password (2)
0
-999
9999
-
IS