EVCO EVFTFT818P7U Installer manual User Manual
Page 68

EVCO S.p.A.
EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214
page 68 of 94
u5
-99
99
°C/°F (1)
2
cabinet temperature over which the door heating elements
are off (4)
u6
1
240
min
5
switching on UV light for sterilisation cycle duration
u7
-99
199
°C/°F (1)
40
needle probe heating end temperature (temperature
detected by the needle probe); see also parameter u8
u8
1
240
min
2
maximum duration of needle probe heating; see also
parameter u7
u9
0
1
- - - -
1
needle probe heating on opening of the door, i.e. on
activation of the door entry micro switch, which occurs after
interruption of a blast chilling and storage cycle or a deep
freezing and storage cycle during storage.
1 = yes
u11
0
1
- - - -
0
utility managed by the output K7 (15)
0 = cabinet light (in this case, the DEEP FREEZING key
and parameters i0 and u2 will assume significance)
1 = UV light (in this case, the DEEP FREEZING key and
parameter u6 will assume significance)
u12
0
999
s
10
compressor switch off delay from pump down valve
deactivation (pump down in switch-off) (17)
Par.
Min.
Max.
Unit
Default
Serial
communication
(RS-48
serial
port
with
MODBUS communication protocol)
L0
- - - -
- - - -
- - - -
- - - -
reserved
L1
1
240
min
5
recording interval during blast chilling and during deep
freezing
L2
1
240
min
15
recording interval during storage
LA
1
247
- - - -
247
device address
Lb
0
3
- - - -
2
baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud