P8
0
1
- - - -
1
orientation of the visualization
0 = device located at the top as to the unit
1 = device located at the bottom as to the unit
Par.
Min.
Max.
Unit
Default
Main regulator
r0
1
15
°C/°F (1)
2
parameters differential r7, r8, r9, r10, r11 and r12
r1
1
500
min
90
duration of time-controlled blast chilling
r2
1
500
min
240
duration of time-controlled deep freezing
r3
-99
99
°C/°F (1)
3
temperature-controlled blast chilling end time temperature;
also end temperature of the temperature-controlled soft
deep freezing phase (temperature detected by the needle
probe); see also parameter r5
r4
-99
99
°C/°F (1)
-18
temperature-controlled deep freezing end temperature
(temperature detected by the needle probe); see also
parameter r6
r5
1
500
min
90
maximum duration of temperature-controlled blast chilling;
see parameter r3 also
r6
1
500
min
240
maximum
duration
of
temperature-controlled
deep
freezing; see parameter r4 also
r7
-99
99
°C/°F (1)
0
work set-point during blast chilling; also work set-point
during the soft deep freezing phase (cabinet temperature);
see also parameter r0
r8
-99
99
°C/°F (1)
-40
work set-point during deep freezing (cabinet temperature);
see also parameter r0
r9
-99
99
°C/°F (1)
-20
work set-point during hard blast chilling phase (cabinet
temperature); see also parameter r0
r10
-99
99
°C/°F (1)
2
work set-point during post blast chilling storage (cabinet
temperature); see also parameter r0
r11
-99
99
°C/°F (1)
-20
work set-point during post deep freezing storage (cabinet
temperature); see also parameter r0
r12
-99
99
°C/°F (1)
5
work set-point during pre-cooling (cabinet temperature);
see also parameter r0