C4
0
240
min
10
duration of compressor switch-off during the cabinet probe
error (“Pr1” code) that occurs during storage; see also
parameters C5 and C9
C5
0
240
min
10
duration of compressor switch-on during the cabinet probe
error (“Pr1” code) that occurs during post blast chilling
storage; see also parameter C4
C6
0
199
°C/°F (1)
80
condenser
temperature
above
which
the
blocked
overheated condenser alarm is activated (“COH” code)
C7
0
199
°C/°F (1)
90
condenser
temperature
above
which
the
blocked
compressor alarm is activated (“CSd” code)
C8
0
15
min
1
blocked compressor alarm delay (“CSd” code) (5)
C9
0
240
min
30
duration of compressor switch-on during the cabinet probe
error (“Pr1” code) that occurs during post deep freezing
storage; see also parameter C4
Par.
Min.
Max.
Unit
Default
Defrosting (6)
d0
0
99
h
8
defrosting interval (7)
0 = defrosting will never be activated at intervals
d1
0
3
- - - -
1
type of defrosting
0 = electrical (the compressor will be switched off during
defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)
1 = hot gas (the compressor will be switched on during
defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)
2 = air (the compressor will be switched off during
defrosting and the defrosting output will be
activated; the evaporator fan will be switched on,
independently from the conditions of the door, i.e.
independently from the door micro switch input
status)
3 = air with door open (the compressor will be switched
off during defrosting and the defrosting output will
be activated; the evaporator fan will be switched on,
on condition that the door is open, i.e. that is on
condition that the door micro switch is active and
that the parameter i0 is set at values different to 0)