16 heating the needle probe, 17 fish sanification – EVCO EVFTFT818P7U Installer manual User Manual
Page 45

EVCO S.p.A.
EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214
page 45 of 94
If the UV light is on, it will not be allowed to select or start any operating cycle.
6.16
Heating the needle probe
Operate as follows:
1.
Make sure the device is in the "on" status or storage is in progress and that the door is open, i.e. the door
micro switch is active.
2.
Make sure that the keyboard is not locked and that no procedure is in progress.
3.
Press and release the
key (1), press and release the
key (2) and then press and release the
START/STOP key (3). The device will display the temperature detected by the needle probe and the cabinet
temperature.
Output K6 is activated at maximum for the time established with parameter u8 or until the temperature detected by
the needle probe reaches that established with parameter u7; closing the door, i.e. the deactivation of the door micro
switch input causes heating to be cut-off.
The buzzer is activated for 2 s on conclusion of heating.
6.17
Fish sanification
The fish sanification cycle is divided into the following three phases:
-
blast chilling
-
maintenance
-
storage.
On conclusion of a phase, the device passes automatically to the next.
Operate as indicated to start the cycle:
1.
Make sure the device is in the "on" status.
2.
Make sure that the keyboard is not locked and that no procedure is in progress.
3.
Press and release the
key (1) and then press and release the
key (2): the device will display the blast
chilling end temperature, the work set-point during blast chilling and the duration of maintenance.