EVCO EVFTFT818P7U Installer manual User Manual
Page 62

EVCO S.p.A.
EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214
page 62 of 94
d2
-99
99
°C/°F (1)
2
defrosting end temperature (evaporator temperature); see
also parameter d3
d3
0
99
min
30
if parameter P4 is set at 0, duration of defrosting
if parameter P4 is s et at 1, maximum duration of
defrosting; see also parameter d2
0 = defrosting will never be activated
d4
0
1
- - - -
0
defrosting on start-up of blast chilling and deep freezing
1 = yes
d5
0
99
min
30
defrosting delay on start-up of storing
0 = defrosting will be started on expiry of the time
established with parameter d0
d7
0
15
min
2
dripping duration (the compressor and the evaporator fan
remain off during dripping and the defrosting output will be
deactivated)
d15
0
99
min
0
minimum duration of compressor switch-on on activation of
defrosting so these can be activated (only if parameter d1 is
set at 1) (8)
d16
0
99
min
0
duration of pre-dripping (only if parameter d1 is set at 1;
the compressor and evaporator fan will be off during pre-
dripping and the defrosting output will remain activated)
Par.
Min.
Max.
Unit
Default
Temperature alarms (9) (10)
A1
0
99
°C/°F (1)
10
cabinet temperature below which the minimum temperature
alarm is activated (relative to the work set-point, i.e. “r10
A1” during post blast chilling storage and “r11 - A1” during
post deep freezing storage; (“AL” code); see also
parameter A11 (4)
A2
0
1
- - - -
1
enabling of minimum temperature alarm (“AL” code)
1 = yes