EVCO EVFTFT818P7U Installer manual User Manual
Page 65
![background image](/manuals/675247/65/background.png)
EVCO S.p.A.
EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214
page 65 of 94
F12
0
240
s
30
condenser fan switch-off delay from compressor switch-off
(only if parameter P5 is set at 0)
F15
0
240
s
15
evaporator fan delay from door closure, i.e. from the
deactivation of the door micro switch input
F16
-99
99
°C/°F (1)
20
evaporator temperature above which the evaporator fan is
off during pre-cooling, blast chilling and deep freezing (only
if parameter F0 is set at 1); see also parameter F8 (11)
F17
-99
199
°C/°F (1)
90
cabinet temperature above which the evaporator fan is off
during pre-cooling, blast chilling and deep freezing (only if
parameter F0 is set at 1 or 2); see also parameter F8
F18
0
100
%
20
evaporator fan speed 1 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F19
0
100
%
40
evaporator fan speed 2 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F20
0
100
%
60
evaporator fan speed 3 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F21
0
100
%
80
evaporator fan speed 4 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”
F22
0
100
%
100
evaporator fan speed 5 (intended as a percentage of the
maximum speed; sonly if parameter F0 is set at 3); see
paragraph 6.12 “Blast chilling/deep freezing intensity”