EVCO EVFTFT818P7U Installer manual User Manual
Page 42

EVCO S.p.A.
EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214
page 42 of 94
storage and parameter F24 establishes the speed at which the evaporator fan is switched on during post deep freezing
storage (the latter intended as one of the speeds 1... 5).
The following table illustrates the speeds at which the evaporator fan is switched on during the operating cycles.
A different speed can be selected using the procedure given in 6.12.1 (intended as one of the speeds 1.. 5) in
temporary mode (i.e. if a power cut occurs, on restore of the same the speeds illustrated in the following table will be
offered), except if the selection is made before starting a blast chilling and storage cycle or before starting a hard blast
chilling and storage cycle or before starting a soft deep freezing and storage cycle (in this case the speeds are
memorised instead).
Blast chilling
and storage
Hard blast
chilling and
storage
Deep freezing
and storage
Soft deep
freezing and
storage
Blast chilling hard phase
-
speed 5
-
-
Blast chilling
speed 1... 5 (can
be memorised
with the
procedure given
in paragraph
6.12.1 if selected
before starting
the operating
cycle)
speed 1... 5 (can
be memorised
with the
procedure given
in paragraph
6.12.1 if selected
before starting
the operating
cycle)
-
-
Deep freezing soft phase
-
-
-
speed 1... 5 (can
be memorised
with the
procedure given
in paragraph
6.12.1 if selected
before starting
the operating
cycle)
Deep freezing
-
-
speed 5
speed 5
Storage
speed established
with parameter
F23
speed established
with parameter
F23
speed established
with parameter
F24
speed established
with parameter
F24