Page 64

background image

EVCO S.p.A.

EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214

page 64 of 94

F0

0

3

- - - -

1

evaporator fan activity during pre-cooling, blast chilling and

deep freezing (if the parameter is set at 3, there will be

effect also during storage)

0 = off, with digital control signal, i.e. via digital output

K3

1 = on, with digital control signal, i.e. via the K3 digital

output; see also parameters F16 and F17

2 = parallel to the compressor, with digital control signal,

i.e. via the K3 digital output; see also parameters F9

and F17

3 = with analogue control signal, i.e. via the PWM

analogue output and the speed regulator phase cut

output

for

EVDFAN1

single

phase

fans

(to order separately); see also parameters F18,

F19, F20, F21, F22, F23 and F24

F1

-99

99

°C/°F (1)

-1

evaporator temperature above which the evaporator fan is

off during storage (only if parameter F0 and/or parameter

F2 is set at 3); see also parameter F8 (11)

F2

0

3

- - - -

3

evaporator fan activity during storage (only if parameter F0

is set at values different to 3)

0 = off

1 = on

2 = parallel to the compressor; see also parameter F9

3 = on; see also parameter F1

F3

0

15

min

2

duration of evaporator fan standstill (the compressor can be

on during evaporator fan standstill, the defrosting output

will remain deactivated and the evaporator fan will remain

off)

F8

1

15

°C/°F (1)

2

F1, F16 and F17 parameters differential

F9

0

240

s

0

evaporator fan switch-off delay from compressor switch off

(only if parameter F0 and/or parameter F2 are set at 2)

F11

0

99

°C/°F (1)

15

condenser temperature above which the condenser fan is

switched on (intended as “F11 + differential and on

condition the compressor is switched off); see also

parameter F12 (4) (12)