F0
0
3
- - - -
1
evaporator fan activity during pre-cooling, blast chilling and
deep freezing (if the parameter is set at 3, there will be
effect also during storage)
0 = off, with digital control signal, i.e. via digital output
K3
1 = on, with digital control signal, i.e. via the K3 digital
output; see also parameters F16 and F17
2 = parallel to the compressor, with digital control signal,
i.e. via the K3 digital output; see also parameters F9
and F17
3 = with analogue control signal, i.e. via the PWM
analogue output and the speed regulator phase cut
output
for
EVDFAN1
single
phase
fans
(to order separately); see also parameters F18,
F19, F20, F21, F22, F23 and F24
F1
-99
99
°C/°F (1)
-1
evaporator temperature above which the evaporator fan is
off during storage (only if parameter F0 and/or parameter
F2 is set at 3); see also parameter F8 (11)
F2
0
3
- - - -
3
evaporator fan activity during storage (only if parameter F0
is set at values different to 3)
0 = off
1 = on
2 = parallel to the compressor; see also parameter F9
3 = on; see also parameter F1
F3
0
15
min
2
duration of evaporator fan standstill (the compressor can be
on during evaporator fan standstill, the defrosting output
will remain deactivated and the evaporator fan will remain
off)
F8
1
15
°C/°F (1)
2
F1, F16 and F17 parameters differential
F9
0
240
s
0
evaporator fan switch-off delay from compressor switch off
(only if parameter F0 and/or parameter F2 are set at 2)
F11
0
99
°C/°F (1)
15
condenser temperature above which the condenser fan is
switched on (intended as “F11 + differential and on
condition the compressor is switched off); see also
parameter F12 (4) (12)