5 time-controlled hard blast chilling and storage – EVCO EVFTFT818P7U Installer manual User Manual
Page 31
EVCO S.p.A.
EVFTFT818 | Installer manual ver. 2.1 | Code 144FTFT818E214
page 31 of 94
During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the duration
of blast chilling.
Parameter r10 establishes the work set-point during storage.
6.5
Time-controlled hard blast chilling and storage
The time-controlled hard blast chilling and storage cycle is divided into the following three phases:
-
blast chilling hard phase
-
blast chilling
-
storage.
On conclusion of a phase, the device passes automatically to the next.
Operate as indicated to start the cycle:
1.
Make sure the device is in the "on" status.
2.
Make sure that the keyboard is not locked and that no procedure is in progress.
3.
Press and release the
key (1), press and release the
key (2) and then press and release the
key (3).
the device will display the blast chilling duration and the work set-point during blast chilling.
4.1
Press and release the MENU key and then press and release the
key or the
key to select the blast chilling
duration and the work set-point during blast chilling.
4.2
Press and release the
key or the
key to modify these values and then the ESCAPE key to memorise them;
these values can also be memorised through parameters r1 and r7.
5.
Press and release the START/STOP key (1): the cycle will be started.