i2
-1
120
min
5
door open alarm signalling delay (“id” code); on expiry of
the time established with the parameter, the compressor
and the evaporator fan will be off
-1 = the alarm will not be signalled
i5
0
1
- - - -
1
effect caused by the activation of the high pressure input
0 = no effect
1 = the compressor and the evaporator fan will be off
and the condenser fan will be on. On expiry of the
time established with parameter i7, the 3 digit
display will show the flashing “HP” code and the
buzzer will be activated (until the input is
deactivated)
i6
0
1
- - - -
0
type of high pressure input 1
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i7
-1
240
s
5
high pressure alarm signalling delay (“HP” code)
-1 = the alarm will not be signalled
i8
0
1
- - - -
0
type of low pressure input 1
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i9
-1
240
s
5
low pressure alarm signalling delay (“LP” code)
-1 = the alarm will not be signalled
i10
0
1
- - - -
0
type of compressor circuit breaker protection input contact
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i11
- - - -
- - - -
- - - -
- - - -
reserved
Par.
Min.
Max.
Unit
Default
Digital outputs
u1
0
1
- - - -
0
utility managed by the output K8 (15)
0 = pump down valve (in this case, parameter u12 will
have meaning)
1 = alarm output