Air Flow Fault Tests – Continued

4. The unit should perform two IGNITION RETRY cycles and then shut down on the third

successive ignition attempt. The unit will display AIRFLOW FAULT DURING PURGE.

5. Re-enable the blower output drive voltage by performing the following steps:

(a)

Press the MENU key until CONFIGURATION MENU is displayed.

(b)

Press the ▲ arrow key until the ANALOG OUTPUT function is displayed, then
press the CHANGE key.

(c)

Press the ▲ arrow key until VALVE POSITION 0-10V is displayed, then press the
ENTER key.

6. Once the unit has proved flame, turn off the blower by going to the Configuration Menu,

Analog Output menu item and select OFF.

7. The Blower Proof Switch will open and the blower should stop. The unit should shut down

and display AIRFLOW FAULT DURING RUN.

8. Go to the Configuration Menu, Analog Output item and select VALVE POSITION 0-10v.

9. Press the CLEAR button. The unit should restart.

10. Next, check the operation of the Blocked Inlet Switch located on the inlet side of the

Air/Fuel Valve (Figure 5-4).

11. Ensure that the sheet metal panels are securely installed on the water heater and the unit

is running.

12. At the rear of the unit, partially block the air inlet (Figure 5-5) with a plywood sheet or

metal plate.

13. The unit should shut down and again display AIRFLOW FAULT DURING RUN.

14. Unblock the air inlet and press the CLEAR button. The unit should restart.

PARTIAL FRONT VIEW

Figure 5-4. Blower Proof & Blocked Inlet Switch Locations

AIR/FUEL

VALVE

BLOWER

BLOCKED INLET
SWITCH

BLOWER PROOF
SWITCH