beautypg.com

3 whm principles of operation, 4 whm menu – AERCO Innovation (G-13-1854 and above) User Manual

Page 110

background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 9 – WATER HEATER MANAGEMENT

Page 110 of

196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0J

PRI: 11/22/2013

Phone: 800-526-0288

GF-128

9.3 WHM PRINCIPLES OF OPERATION

The WHM system communicates with the plant water heaters via a RS485 network utilizing
Modbus RTU protocol (8 bit, 9600 baud, no parity). All Modbus networks are implemented using
a Master/Slave scenario where only one device, the Master, can initiate a communication
sequence. All other C-More equipped units on the network are called Slaves. However, since
the WHM software code resides in each C-More that is part of the system, any one of the C-
Mores can be selected to control the system.

The controlling Master monitors the Air/Fuel Valve position (VP) of all enabled units. When this
valve position (% open) exceeds a user-selectable limit (WHM Nxt On VP), the WHM will open
the sequencing valve of another water heater in the system. Conversely, when the valve
positions of all enabled units have dropped below a different user-selectable limit (WHM Nxt Off
VP) threshold, the WHM will close the sequencing valve on a unit. The philosophy behind this
approach is to maintain the fire rates (Air/Fuel Valve % open) at a level that maximizes heater
efficiency.

In addition to collecting Air/Fuel Valve position data, the controlling Master also monitors the
total accumulated operating time for each unit on the system and attempts to balance the
system so that all units operate for approximately the same number of hours.

9.4 WHM MENU

The WHM Menu in each C-More can only be viewed when the Unit Type option in the
Configuration Menu is set to Innovation WH. The WHM Menu contains only ten (10) user-
selectable menu options. In addition, these menu options are listed in Table 9-1. Descriptions
for each menu item are included in Appendix A.

NOTE

In addition to the WHM Menu items listed in Table 9-1, the Setup Menu
contains a Comm Address option which must be entered for each unit to
enable WHM control of the system.

Table 9-1. WHM Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

WHM Mode

Off, WHM Slave,

WHM Master

Off

WHM Setpoint

40°F

200°F

130°F

WHM Nxt On VP

16%

100%

75%

WHM Nxt Off VP

16%

100%

35%

Lead/Lag Hours

25

225

72

Setback Setpoint

40°F

220°F

130°F

Setback Start

12:00am

11:59pm

12:00am

Setback End

12:00am

11:59pm

12:00am

WHM Auto Mstr

Yes or No

No

WHM Auto Timer

10 sec.

120 sec.

30 sec.