INNOVATION DEFAULT SETTINGS - Continued

MENU & OPTION

FACTORY DEFAULT

Tuning Menu

Prop Band

8°F

Integral Gain

1.60

Derivative Time

0.10 min

Min Load Adj

0°F

Max Load Adj

0°F

FFWD Temp

N/A

Outlet Feedback

On

Feedback Gain

0.05

Breakpoint At 100%

85°F

Breakpoint At 90%

86°F

Breakpoint At 80%

87°F

Breakpoint At 70%

88°F

Breakpoint At 60%

89°F

Breakpoint At 50%

90°F

Breakpoint At 40%

94°F

Breakpoint At 30%

103°F

Breakpoint At 20%

118°F

Breakpoint At 10%

134°F

Breakpoint At 0%

136°F