beautypg.com

Appendix d – innovation default settings – AERCO Innovation (G-13-1854 and above) User Manual

Page 133

background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

APPENDIX D – INNOVATION DEFAULT SETTINGS

OMM-0078_0J

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 133 of

196

GF-128

Phone: 800-526-0288

PRI: 11/22/2013

APPENDIX D – INNOVATION DEFAULT SETTINGS

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password

0

Language

English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

Innovation WH

Unit Size

600 MBH, 800 MBH, 1060 MBH, 1350 MBH

Fuel Type

Natural Gas

Heater Mode

Constant Setpoint

Remote Signal

(If Heater Mode = Remote Setpoint)

4 – 20 mA ,/ 1-5V

Outdoor Sensor

Disabled

Setpt Lo Limit

60°F

Setpt Hi Limit

200°F

Temp Hi Limit

160°F

Max Valve Position

100%

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

mA Output

Off

Lo Fire Timer

2 sec.

Setpt Limiting

Disabled

Setpt Limit Band

0°F

Network Timeout

30 seconds

HI DB Setpt En

30

Demand Offset

0

Deadband High

0

Deadband Low

0