CHAPTER 3 – OPERATION

Page 46 of

196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0J

PRI: 11/22/2013

Phone: 800-526-0288

GF-128

3. With all required safety device switches closed, a purge cycle will be initiated and the

following events will occur:

(a)

The Blower relay energizes and turns on blower.

(b)

The Air/Fuel Valve rotates to the full-open purge position and closes purge
position switch. The dial on the Air/Fuel Valve (Figure 3-4) will read 100 to
indicate that it is full-open (100%).

(c)

The VALVE POSITION bargraph will show 100%.



Figure 3-4. Air/Fuel Valve In Purge Position

4. Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will

show Purging and indicate the elapsed time of the purge cycle in seconds.

Figure 3-5. Blower Proof Switch

STEPPER
MOTOR

TO BLOWER

AIR IN

PURGE

VALVE POSITION

DIAL AT 100%

BLOWER PROOF
SWITCH

OUTLET TO BLOWER

AIR/FUEL
VALVE