beautypg.com

6 configuration menu – AERCO BMK 6000 Dual Fuel User Manual

Page 44

background image

Benchmark 6000 DF Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

Page 44 of 219

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0096_0B

03/21/2014

Ph.: 800-526-0288

GF-141

Table 3-3: Setup Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Password

0

9999

0

Language

English

English

Time

12:00 am

11:59 pm

Date

01/01/00

12/31/99

Unit of Temp

Fahrenheit or Celsius

Fahrenheit

Comm Address

0

127

0

Baud Rate

2400, 4800, 9600, 19.2K

9600

Upload Timer

0

0

Unit Alpha

A

Z

A

Unit Serial #

0000

9999

0000

Unit Year

0

99

00

C-More Year

0

99

11

C-More Serial #

0

9999

0000

C-More Alpha

A

Z

A

IP Address

Software

Ver 0.00

Ver 9.99

3.6 CONFIGURATION MENU

The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt)
temperature regardless of whether the valid password has been entered. Setpt is required for
operation in the Constant Setpoint mode. The remaining options in this menu require the valid
password to be entered, prior to changing existing entries. This menu contains a number of other
configuration settings which may or may not be displayed, depending on the current operating
mode setting.

NOTE

The Configuration Menu settings shown in Table 3-4 are Factory-Set in
accordance with the requirements specified for each individual order.
Therefore, under normal operating conditions, no changes will be required.