Table B-2: Fault Messages – Continued

FAULT MESSAGE

FAULT DESCRIPTION

IGN SWTCH OPEN

DURING IGNITION

The Ignition Position Limit switch on the Air/Fuel Valve
opened during ignition.

INTERLOCK

OPEN

The Remote Interlock is open.

LINE VOLTAGE

OUT OF PHASE

The Line (Hot) and Neutral wires are reversed.

LOW WATER

LEVEL

The Low Water Cutoff board is indicating low water level.

MODBUS COMM

FAULT

The RS-485 network information is not present or is
corrupted.

O2 PERCENTAGE

LOW

The O2 percentage measured by the O2 sensor is below
??%

O2 SENSOR

MALFUNCTION

A fault exists in the O2 sensor.

OUTDOOR TEMP

SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out
of range.

OUTLET TEMP

SENSOR FAULT

The temperature measured by the Outlet Sensor is out of
range:
OUTLET TEMPERATURE display = SHt Indicates sensor is
shorted
OUTLET TEMPERATURE display = Opn indicates sensor is
open-circuited

PRG SWTCH CLOSED

DURING IGNITION

The Purge Position Limit Switch on the Air/Fuel Valve closed
during ignition.

PRG SWTCH OPEN

DURING PURGE

The Purge Position Limit Switch on the Air/Fuel Valve
opened during purge.

REMOTE SETPT

SIGNAL FAULT

The Remote Setpoint signal is not present or is out of range.

RESIDUAL

FLAME

The flame signal was seen for more than 60 seconds during
standby.

SSOV

SWITCH OPEN

The SSOV switch opened during standby.

SSOV FAULT

DURING PURGE

The SSOV switch opened during purge.