Benchmark 6000 DF Installation, Operation & Maintenance Manual
APPENDIX J – RECOMMENDED PERIODIC TESTING
Page 206 of 219
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0096_0B
03/21/2014
Ph.: 800-526-0288
GF-141
Item
Frequency
Accomplished
By
Remarks
High water
temperature safety
control test
Annually
Service
Technician
See section 6.5
Operating controls
Annually
Operator
See section 3.2
Low air flow
Monthly
Operator
See section 6.8
Low and high gas
pressure interlocks
Monthly
Operator
See sections 6.2 and 6.3
Air/Fuel Valve purge
position switch
Annually
Service
Technician
See section 6.10
Air/Fuel Valve ignition
position switch
Annually
Service
Technician
See section 6.11
Safety valves
As required
Operator
Check per A.S.M.E. Boiler and
Pressure Vessel Code, Section IV
Inspect Burner
components
Semi-
Annually
Service
Technician
See section 7.7
Condensate Trap
Semi-
Annually
Operator
See section 7.9
Oxygen (O
2
) Level
Monthly
Operator
Verify oxygen level is between 3% and
8% during boiler operation
Pilot Sensor
Semi-
Annually
Operator
Red LED should be on when operating
Pilot View Port
Monthly
Operator
Turn off boiler first.