background image

Benchmark 6000 DF Installation, Operation & Maintenance Manual

APPENDIX A – BOILER MENU DESCRIPTIONS

OMM-0096_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 157 of 219

GF-141

Ph.: 800-526-0288

03/21/2014

APPENDIX A: BOILER MENU ITEM DESCRIPTIONS – Continued

MENU LEVEL & OPTION

DESCRIPTION

CONFIGURATION MENU

Unit Size

Sets unit size from 600 MBH to 6000 MBH
depending on the Unit Type.

Fuel Type

Allows selection of Natural Gas or Propane

Boiler Mode

It allows selection of: Constant Setpoint, Remote
Setpoint, Direct Drive, Combination, or Outdoor
Reset Mode. Default is Constant Setpoint Mode.

Remote Signal

Used to set the type of external signal which will be
used when operating in the Remote Setpoint, Direct
Drive or Combination Mode. The factory default is
4-20 mA/1-5V.

Bldg Ref Temp

Allows the building reference temperature to be set
when operating a boiler in the Outdoor Reset Mode.
Default is 70°F.

Reset Ratio

Permits setting of Reset Ratio when operating boiler
in the Outdoor Reset Mode. Reset Ratio is
adjustable from 0.1 to 9.9. Default is 1.2.

Outdoor Sensor

Allows outdoor sensor function to be enabled or
disabled. Default is disabled.

System Start Tmp

If outdoor sensor is enabled, this menu item allows
the system start temperature to be set from 30 to
100°F. Default is 60°F.

Setpoint Lo Limit

Used to set the minimum allowable setpoint (40°F to
Setpoint Hi Limit). Default is 60°F

Setpoint Hi Limit

Used to set the maximum allowable setpoint
(Setpoint Lo Limit to 210°F). Default is 140°F.

Temp Hi Limit

This is the maximum allowable outlet temperature
(40 to 210°F). Any temperature above this setting
will turn off the unit. The temperature must then drop
5° below this setting to allow the unit to run. Default
Hi Limit is 160°F.

Max Valve Position

Sets the maximum allowable valve position for the
unit (40% to 100%). Default is 100%.

Pump Delay Timer

Specifies the amount of time (0 to 30 min.) to keep
the pump running after the unit turns off. Default is
zero.