SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors
4
Installation Guide
Normal (Configuration) Menu
Press and release the MENU button to enter the
configuration menu:
1. BUZZER TRIP=150: The factory default for the
buzzer trip level is 150 ppm. This can be changed
by using the ROLL button from 100 to 400 ppm
in increments of 10 ppm. Use the SAVE button to
save any change to memory.
Press the MENU button.
2. BUZZER DEL=5MIN: The factory default is 5
minutes and this can be changed with the ROLL
button to 0, 1, 2, 3, 4 or 5 minutes. Use the SAVE
button to save any changes to memory.
Press the MENU button.
3. BUZZER ENABLE: The factory default is
ENABLE. It can be changed to DISABLE with the
ROLL button. Use SAVE to save any changes to
memory. If this is set to DISABLE the buzzer will
never sound.
Press the MENU button.
4. RELAY1 TRIP=50: The factory default Relay1 trip
level is 50 ppm. Use the ROLL button to change it
to 25 or to 40–350 ppm in increments of 10 ppm.
The SAVE button saves any changes.
Press the MENU button.
5. RELAY1 HYST=10: The factory default for Relay1
hysteresis (deadband) is 10 ppm. Change using
the ROLL button to 10, 15, 25, 50, or 75 ppm. Save
using the SAVE button.
NOTE: RELAY1 HYST is always less than RELAY1
TRIP and may not display all options.
Press the MENU button.
6. RELAY1 DEL=2MIN: The factory default is 2
minutes and this can be changed with the ROLL
button to 0, 1, 2, 3, 4, or 5 minutes. Save using the
SAVE button.
Press the MENU button.
7. RELAY2 TRIP=150: The factory default Relay2
trip level is 150 ppm. Use the ROLL button to
change it to 100–400 ppm in increments of 10
ppm. The SAVE button saves any changes.
Press the MENU button.
8. RELAY2 HYST=25: The factory default for Relay2
hysteresis (deadband) is 25 ppm. Change using
the ROLL button to 10, 15, 25, 50, or 75 ppm. Save
using the SAVE button.
Press the MENU button.
9. RELAY2 DEL=2MIN: The factory default is 2
minutes and this can be changed with the ROLL
button to 0, 1, 2, 3, 4, or 5 minutes. Save using the
SAVE button.
Press the MENU button. Returns to normal
operation.
Test Menu
1. OUTPUT TEST 4mA/0V: This item tests the
analog output (current or voltage depending on
the jumper position). Use the ROLL button to
change the output signal to 4, 8, 12, 16, or 20 mA
or 0, 1, 2, 3, 4, or 5 VDC.
NOTE: If 10 VDC output is selected by jumpers, the
output voltage will be double the display.
Press the MENU button.
2. BUZZER TEST OFF: If installed, use the ROLL
button to turn the buzzer ON or OFF. Use SAVE
to exit the menu.
Press the MENU button.
3. RELAY1 TEST OFF: If installed, use the ROLL
button to turn the relay ON or OFF. Use SAVE to
exit the menu.
Press the MENU button.
4. RELAY2 TEST OFF: If installed, use the ROLL
button to turn the relay ON or OFF. Use SAVE to
exit the menu.
Press the MENU button. Returns to normal
operation.
Calibration Menu
1. SENSOR (ECON300): The sensor type and range
are indicated on the LCD. Do not change this
setting.
Press the MENU button.
2a. CALIBRAT 20mA x: If set for current output,
this item allows calibration of the 20 mA output
signal. Connect a meter to the output and use the
ROLL button to set the output to exactly 20.0 mA.
Use the SAVE button to save any change.
Press the MENU button.
2b. CALIBRAT 5V x: If set for current output, this
item allows calibration of the 5 VDC output
signal. Be sure the 5VDC output jumper positions
are selected, connect a meter to the output, and
use the ROLL button to set the output to exactly
5.0 VDC. Save using the SAVE button.
Press the MENU button.
3. RESTORE DEFAULTS: Press the SAVE button
here to restore all factory defaults to their original
settings as when shipped from the factory.
Press the MENU button. Returns to normal
operation.