beautypg.com

Wiring, Caution – KMC Controls SAE-1152(NEW Style Board) User Manual

Page 2

background image

SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors

2

Installation Guide

Use 22 AWG shielded wiring for all connections.

Do not locate device wires in the same conduit with

wiring used to supply inductive loads.
1. Connect the positive DC voltage, or the hot

side of the AC voltage, to the terminal marked

POWER (but do not apply power until all wiring

is completed).

2. Connect the power supply common to the

terminal marked COM. The device is reverse

voltage protected and will not operate if

connected backwards.

NOTE: The detectors have a half-wave power

supply with the common the same as the

output signal common. If several units are

connected to one power supply, output

signals share the same signal common.

However, KMC recommends using a

separate transformer for each device.

CAUTION

Use caution when grounding the secondary of an
AC transformer, or when wiring multiple devices,
to ensure that the circuit ground point is the same
on all devices and the controller. See Application
Note AN0604D “Tips for connecting-volt power”
available from the KMC Controls web site or in the
SP-022 Digital Designer Guide.

3. Select the desired analog signal output jumper

for either Current (4–20 mA) or Voltage. A second

jumper selects either 0–5 VDC output or 0–10

VDC.

CAUTION

The 4-20 mA current output signal operates in the
active mode and does not require a loop power
supply. The signal current is generated by the SAE-
1100 series detector and must not be connected to a
powered input or device damage will result.

4. Set the input jumpers/pull-up resistors on the

KMDigital or BACnet controller for the desired

active voltage or current according to the

controller’s instructions.

5. Connect the detector’s OUT terminal to the

controller’s input (referenced to the COM

terminal) according to the illustration below.

NOTE: The sets of form “C” relays feature

Normally

Open (NO), Normally Closed (NC), and

Relay Common (R.COM) terminals. The

relay output is completely isolated and

has both NO and NC signals. The R.COM

terminal is NOT connected to the signal or

power supply COMMON terminal.

NOTE: See also Application Note AN0504L

“Connecting inputs and outputs to KMC

controllers” available from the KMC

Controls web site or in the SP-022 Digital

Designer Guide.

Wiring

NOTE: These instructions apply to units

manufactured after the corresponding

dates shown in the Models list. For older

units (with a row of LEDs on the left side

of the board), see the original version of

this installation guide available on www.

kmccontrols.com.

This manual is related to the following products: