Fan coil unit (fcu), 2 or 4 pipe, modulating or 2 position 8, 2 or 4 pipe, modulating or 2 position – KMC Controls BAC-14xx63 Series FlexStat User Manual
Page 8

BAC-12xx63/13xx63/14xx63 Series FlexStat
8
Installation Guide, Rev. C
4-PIPE MODULATING OPTION
(See the FCU—Other Options section on the next page for more options)
VEP-45xxB745/
VEB-43xxxBCK
Valves with
MEP-4002 0–10
VDC Actuators
XEE-6311-050 Transformer
REE-3211 or CVR11C-0/LD96200 Multi-Voltage Relays
FCU 4-PIPE
MODULATING LAYOUT
CSE-1102 Air Differential
Pressure Switch
NOTE: EITHER FAN STATUS (FST) OR
DISCHARGE AIR TEMP (DAT) CAN
BE USED ON IN2, BUT NOT BOTH.
STE-1402 Duct
Sensor, Type III
Fan Coil Unit (FCU)—
2 or 4 Pipe, Modulating or 2 Position
Output Terminals
(BAC-12xxx63C)
FCU Output Connections
BACnet
Objects
2-Pipe
4-Pipe
Analog 9
AO9
GND
Ground
(for analog output terminals 7–9)
Analog 8
Heat Valve,
Proportional (HTV)
AO8
Analog 7
Valve,
Proportional (VLV)
Cool Valve,
Proportional (CLV)
AO7
Relay 6
BO6
SC 4–6
24 VAC (for relay terminals 4–6)
Relay 5
Heat Valve,
2-Position (HTV)
BO5
Relay 4
Valve,
2-Position (VLV)
Cool Valve,
2-Position (CLV)
BO4
Relay 3
Fan 3
BO3
SC 1–3
24 VAC (for relay terminals 1–3)
Relay 2
Fan 2
BO2
Relay 1
Fan 1
BO1
*If optional Outside Air Damper is used, must also have MAT/OAT inputs.
APPLICATION
DEGREES SCALE: °F
APP:
OPT: 4–PIPE
ADDITIONAL SETUP
FAN COIL
ADDITIONAL SETUP
FAN
HUMIDITY
OPTIMUM START
SENSORS
VALVE
NOTE: To see
Humidity
options in the
Additional
Setup menu,
select the 4-Pipe
option.
NOTE: Do not
use REE-3211/
CVR11C-0/
LD96200 relays
with analog
outputs! See
Output Connec-
tions on page 3.
Input Terminals
FCU Input Connections
BACnet Objects
IN9
Opt. Remote CO
2
Sensor*
AI9
IN8
AI8
IN7
Opt. Remote Temp. Sensor*
AI7
IN4
AI4
IN3
Supply Water Temp. (W-TMP)**
AI3
GND
Ground
IN2
Optional FST or DAT*
AI2
*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown
on the diagram) remote temp./CO
2
sensors are optional inputs. Set
pull-up resistor switch positions appropriately (see the Input
Connections section).
**W-TMP is for 2-pipe applications only (see drawings on the next page)
NOTE: Do not use REE-3211/
CVR11C-0/LD96200
relays
with analog outputs! See Output
Connections on page 3.