Fan coil unit (fcu), 2 or 4 pipe, modulating or 2 position 8, 2 or 4 pipe, modulating or 2 position – KMC Controls BAC-14xx63 Series FlexStat User Manual

Page 8

background image

BAC-12xx63/13xx63/14xx63 Series FlexStat

8

Installation Guide, Rev. C

4-PIPE MODULATING OPTION

(See the FCU—Other Options section on the next page for more options)

VEP-45xxB745/
VEB-43xxxBCK

Valves with

MEP-4002 0–10

VDC Actuators

XEE-6311-050 Transformer

REE-3211 or CVR11C-0/LD96200 Multi-Voltage Relays

FCU 4-PIPE

MODULATING LAYOUT

CSE-1102 Air Differential

Pressure Switch

NOTE: EITHER FAN STATUS (FST) OR

DISCHARGE AIR TEMP (DAT) CAN
BE USED ON IN2, BUT NOT BOTH.

STE-1402 Duct
Sensor, Type III

Fan Coil Unit (FCU)—

2 or 4 Pipe, Modulating or 2 Position

Output Terminals

(BAC-12xxx63C)

FCU Output Connections

BACnet

Objects

2-Pipe

4-Pipe

Analog 9

AO9

GND

Ground

(for analog output terminals 7–9)

Analog 8

Heat Valve,

Proportional (HTV)

AO8

Analog 7

Valve,

Proportional (VLV)

Cool Valve,

Proportional (CLV)

AO7

Relay 6

BO6

SC 4–6

24 VAC (for relay terminals 4–6)

Relay 5

Heat Valve,

2-Position (HTV)

BO5

Relay 4

Valve,

2-Position (VLV)

Cool Valve,

2-Position (CLV)

BO4

Relay 3

Fan 3

BO3

SC 1–3

24 VAC (for relay terminals 1–3)

Relay 2

Fan 2

BO2

Relay 1

Fan 1

BO1

*If optional Outside Air Damper is used, must also have MAT/OAT inputs.

APPLICATION

DEGREES SCALE: °F

APP:

OPT: 4–PIPE
ADDITIONAL SETUP

FAN COIL

ADDITIONAL SETUP

FAN

HUMIDITY
OPTIMUM START
SENSORS
VALVE

NOTE: To see

Humidity

options in the

Additional

Setup menu,

select the 4-Pipe

option.

NOTE: Do not

use REE-3211/

CVR11C-0/

LD96200 relays

with analog

outputs! See

Output Connec-

tions on page 3.

Input Terminals

FCU Input Connections

BACnet Objects

IN9

Opt. Remote CO

2

Sensor*

AI9

IN8

AI8

IN7

Opt. Remote Temp. Sensor*

AI7

IN4

AI4

IN3

Supply Water Temp. (W-TMP)**

AI3

GND

Ground

IN2

Optional FST or DAT*

AI2

*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown

on the diagram) remote temp./CO

2

sensors are optional inputs. Set

pull-up resistor switch positions appropriately (see the Input

Connections section).

**W-TMP is for 2-pipe applications only (see drawings on the next page)

NOTE: Do not use REE-3211/

CVR11C-0/LD96200

relays

with analog outputs! See Output

Connections on page 3.