beautypg.com

Setpoint calibration, Remote setpoint adjustment, Accessories – KMC Controls CCC-1002 User Manual

Page 3: Maintenance

background image

CCC-1001/1002 (Dual Input Receiver Controllers)

3

Installation Guide

Setpoint Calibration

Initial setpoint calibration is done after the spring

tube on the back of the controller has been properly

connected and secured and the throttling range and

authority adjustments have been set and locked.
1. Make the following connections:

A. Main air supply (20 psi) to MAIN.
B. Branch (output) gauge to Port B.
C. For SINGLE input operation, connect

pressure to Port 1 equal to the desired

setpoint, OR for DUAL input operation,

connect pressures to Ports 1 and 3 that

correspond to the reset schedule at

approximately midrange.

D. If the remote setpoint adjustment is to

be used, connect pressure to Port 2 that

corresponds to zero offset.

E. Unused inputs are left unconnected.

2. Turn the setpoint adjustment screw to obtain an

output equal to the midrange pressure of the

controlled device.

A. If in the DA mode and branch pressure

is high, turn the setpoint screw CW; if

branch pressure is low, turn the setpoint

screw CCW.

B. If in the RA mode and branch pressure

is high, turn the setpoint screw CCW; if

branch pressure is low, turn the setpoint

screw CW.

After the system is live, minor adjustments to the

setpoint calibration can easily be done if the setpoint

offset is known. Each complete clockwise rotation, of

the screw, is equivalent to a 1.75 psi increase in Port

1 pressure. To increase the setpoint, turn the adjust-

ment screw CW; to decrease the setpoint, turn the

adjusment screw CCW. The number of turns equals:

Setpoint Offset (° F)

Port 1 Primary Input Span

(° F)

x

Port 1 Primary Input Span (psi)

1.75

Example: Port 1 is connected to a temperature

transmitter with a range of 40 to 240° F

(200° F span) and an output of 3 to 15 psi

(12 psi span). The desired control point is

7° F higher than the actual control point.

Then, the number of turns = (7°)/(200°)

x (12 psi)/1.75 = 0.24. Thus, the set point

adjustment screw should be turned 1/4 of a

turn CW.

Remote Setpoint Adjustment

An input pressure change of 3 to 15 psi to Port 2 will

change the setpoint 20% of the span of the primary

transmitter. The effect of the change is direct in

nature. An increase in Port 2 pressure from 9 to 15

psi increases the setpoint 10% and a decrease in Port

2 pressure from 9 to 3 psi decreases the setpoint 10%.

Example: If the Port 1 transmitter has a range of 40

to 240° F (200° F span), then the remote

setpoint adjustment pressure on Port 2 can

change the setpoint +/– 20° F or a total of

40° F or 20% of the Port 1 primary input

span.

Maintenance

No routine maintenance is required. Each compo-

nent is designed and manufactured for reliability

and performance. Careful installation will ensure

long term dependability.

Accessories

External restrictor HFO-0022 (Restrictor T, 28.8 scim)

might be required if replacing a receiver/controller

using internal restrictors. All transmitters used with

the CCC-1001/1002 require an external restrictor.
For other pneumatic accessories, such as connectors,

tubing, fittings, filters, and gauges, see the Com-

pressed Air Accessories section in the Electronic and

Pneumatic Controls Condensed Catalog (SP-071).

This manual is related to the following products: