CCC-1001/1002 (Dual Input Receiver Controllers)

2

Installation Guide

Authority Calibration

This adjustment determines the effect of a secondary

transmitter (Port 3) on the setpoint of the receiver-

controller.

Example: Reset the HWS (Hot Water Supply)

temperature setpoint based on OAT

(Outside Air Temperature). The HWS

transmitter has a range of 40 to 240° F for 3

to 15 psi (0.06 psi/° F), and it is connected

to the Port 1 primary input. The OAT

transmitter has a range of –40 to 160° F for 3

to 15 psi (0.06 psi/° F), and it is connected to

the Port 3 secondary input.

NOTE: This example does not compensate for TR

(throttling range) across the reset schedule

but assumes a constant branch pressure.

The reset schedule shows the temperatures and pres-

sures at the extreme ends of the operating schedule.

Adjustments and Calibration

Throttling Range Adjustment

Throttling range % can be calculated by the follow-

ing formula:

Port 1 Units Desired to Make

100% Change in Port B (Output)

Port 1 Primary Input Span

(Same Units as Above)

x

12

Span of Controlled

Device (psi)

x 100

Example: Port 1 is connected to a temperature

transmitter with a range of 40 to 240° F

(200° F span). Branch output is controlling

a 3 to 8 psi (5 psi span) device. Desired

throttling range is 20° F. Then throttling

range % = (20° F)/(200° F) x (12 psi)/(5 psi) x

100 = 24%.

D P @ Port 1
D P @ Port 3

x 100%

Reset Schedule

OAT Port #3

Pressure

Outside Air

Temperature

Hot Water

Temperature

HWS Port #1

Pressure

5.4 psi

0° F

180° F

11.4 psi

7.5 psi

35° F

140° F

9.0 psi

9.6 psi

70° F

100° F

6.6 psi

Authority % =

(D P = Change in Pressure)

=

11.4 – 6.6
9.6 – 5.4

x 100% = 114%

CCC-1001 Controller

NOTE: Throttling range is the percent change of

the primary input (Port 1) that causes a

100% change in the branch output (Port B).

Authority is the change in the secondary

input (Port 3) in relation to the change in

the primary input that will cause the same

change in the output and is expressed as a

percentage (see the Authority Calibration

section).

1. Remove cover before making any adjustments.
2. Set the desired throttling range:

A. Loosen large center screw (1 turn

maximum).

B. Remove main control air from Port M.
C. Move the setpoint indicator to the desired

% throttling range (4 to 40%) on the DA

or RA scale. See the Throttling Range

Adjustment section on page 3.

D. Connect main air to “M.”

3. Set the desired authority:

A. Calculate the required authority. See the

Authority Calibration section.

B. Set the authority indicator to the desired

value.

C. Tighten center screw.

4. Adjust the setpoint output by turning the setpoint

screw (located at the lower right of the unit). See

the Setpoint Calibration section on page 3.

5. Reinstall the cover.

CCC-1002 Controller

NOTE: Follow the steps 1 through 4 for adjusting

the CCC-1001, and then continue with steps

5 through 8.

5. Turn the face dial until the desired input signal

(Port 1) pressure value lines up with the clear

arrow indicator.

6. Carefully slide the cover straight down, so that

the cover gear teeth and the setpoint adjustment

shaft mesh.

7. Tighten the cover.
8. Apply the adhesive dial face if required.

(In the Example Above)