Acceptable grounding practices, Figure 18 – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 53

background image

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

53

Grounding Chapter 3

Figure 18 - Fully Grounded Scheme

The installation and grounding practices to reduce common mode noise issues
can be categorized into three ratings. The scheme used must consider additional
costs against the operating integrity of all scheme components. If no sensitive
equipment is present and noise is not an issue, the added cost of shielded cable
and other components is not always justified.

Acceptable Grounding Practices

The scheme shown below is an acceptable ground layout for a single drive
installation. However, conduit does not offer the lowest impedance path for any
high frequency noise. If the conduit is mounted so that it contacts the building
steel, it is likely that the building steel offers a lower impedance path and causes
noise to inhabit the ground grid.

Earth Ground Potential

X0

R

S

T

U

V

W

PE

PE

A

B

C

PE

Input Transformer

AC Drive

Conduit

Motor Frame

Motor

Connection to Drive

Structure or Optional

Cabinet Via Conduit

Connector

Strap

Incidental Contact

of Conduit Strap

Motor Frame

Ground

Connection to Ground Grid,

Girder, or Ground Rod

Connection to Cabinet Ground Bus

or Directly to Drive PE Terminal

Panel Ground Bus

Optional Enclosure

Building Ground Potential