160 drives – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 128
128
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Appendix A Motor Cable Length Restrictions Tables
160 Drives
This section lists motor cable data for 160 drives.
Table 58 - 160 Drives, 480V – Meters (Feet)
Table 59 - 160 Drive, 240V and 480V – Cable Charging Current – Meters (Feet)
380…460V
Ratings
Motor Insulation Rating -
VoltsP-P
Motor Cable Only
RWR at Drive
Reactor at Motor
Shielded Unshielded
Shielded
Unshielded
Shielded
Unshielded
4.0 kW
(5 Hp)
1000
13.7 (45)
6.1 (20)
160.0 (525)
182.9 (600)
99.1 (325)
91.4 (300)
1200
27.4 (90)
12.2 (40)
160.0 (525)
182.9 (600)
160.0 (525)
129.5 (425)
1600
160.0 (525)
144.8 (475)
160.0 (525)
182.9 (600)
160.0 (525)
182.9 (600)
2.2 kW
(3 Hp)
1000
12.2 (40)
12.2 (40)
160.0 (525)
182.9 (600)
68.6 (225)
76.2 (250)
1200
27.4 (90)
18.3 (60)
160.0 (525)
182.9 (600)
99.1 (325)
129.5 (425)
1600
160.0 (525)
152.4 (500)
160.0 (525)
182.9 (600)
160.0 (525)
182.9 (600)
1.5 kW
(2 Hp)
1000
12.2 (40)
12.2 (40)
129.5 (425)
182.9 (600)
99.1 (325)
91.4 (300)
1200
27.4 (90)
18.3 (60)
129.5 (425)
182.9 (600)
129.5 (425)
137.2 (450)
1600
152.4 (500)
152.4 (500)
129.5 (425)
182.9 (600)
164.6 (540)
182.9 (600)
0.75 kW
(1 Hp)
1000
16.8 (55)
12.2 (40)
99.1 (325)
182.9 (600)
99.1 (325)
106.7 (350)
1200
38.1 (125)
18.3 (60)
99.1 (325)
182.9 (600)
152.4 (500)
137.2 (450)
1600
152.4 (500)
152.4 (500)
99.1 (325)
182.9 (600)
152.4 (500)
182.9 (600)
0.55 kW
(0.75 Hp)
1000
13.7 (45)
12.2 (40)
91.4 (300)
182.9 (600)
91.4 (300)
91.4 (300)
1200
38.1 (125)
18.3 (60)
91.4 (300)
182.9 (600)
152.4 (500)
152.4 (500)
1600
152.4 (500)
152.4 (500)
91.4 (300)
182.9 (600)
152.4 (500)
182.9 (600)
0.37 kW
(0.5 Hp)
1000
13.7 (45)
27.4 (90)
91.4 (300)
129.5 (425)
91.4 (300)
129.5 (425)
1200
38.1 (125)
54.9 (180)
91.4 (300)
129.5 (425)
152.4 (500)
152.4 (500)
1600
152.4 (500)
152.4 (500)
91.4 (300)
129.5 (425)
152.4 (500)
152.4 (500)
480V
Ratings
kHz
Motor Cable Only
RWR at Drive (NR = not recommended) Reactor at Motor
Shielded
(1)
(1) When you use shielded cable at lightly loaded conditions, cable length recommendations for drives rated 0.75 kW (1 Hp) and below are 61 m (200 ft).
Unshielded
Shielded
Unshielded
Shielded
Unshielded
4.0 kW
(5 Hp)
2
106.7 (350)
182.9 (600)
91.4 (300)
182.9 (600)
121.9 (400)
182.9 (600)
4
129.5 (425)
182.9 (600)
106.7 (350)
182.9 (600)
137.2 (450)
182.9 (600)
8
144.8 (475)
152.4 (500)
NR
NR
137.2 (450)
152.4 (500)
2.2 kW
(3 Hp)
2
109.7 (360)
182.9 (600)
85.3 (280)
182.9 (600)
121.9 (400)
182.9 (600)
4
114.3 (375)
182.9 (600)
83.8 (275)
182.9 (600)
121.9 (400)
182.9 (600)
8
121.9 (400)
152.4 (500)
NR
NR
121.9 (400)
152.4 (500)
1.5 kW
(2 Hp)
2
91.4 (300)
167.6 (550)
83.8 (275)
182.9 (600)
91.4 (300)
182.9 (600)
4
91.4 (300)
167.6 (550)
83.8 (275)
182.9 (600)
91.4 (300)
152.4 (500)
8
99.1 (325)
152.4 (500)
NR
NR
106.7 (350)
152.4 (500)
0.75 kW
(1 Hp)
2
61.0 (200)
114.3 (375)
61.0 (200)
129.5 (425)
68.6 (225)
121.9 (400)
4
68.6 (225)
114.3 (375)
61.0 (200)
129.5 (425)
68.6 (225)
114.3 (375)
8
76.2 (250)
114.3 (375)
NR
NR
68.6 (225)
121.9 (400)
0.55 kW
(0.75 Hp)
2
54.9 (180)
106.7 (350)
54.9 (180)
114.3 (375)
54.9 (180)
106.7 (350)
4
54.9 (180)
106.7 (350)
54.9 (180)
114.3 (375)
54.9 (180)
106.7 (350)
8
54.9 (180)
106.7 (350)
NR
NR
54.9 (180)
106.7 (350)
0.37 kW
(0.5 Hp)
2
30.5 (100)
99.1 (325)
30.5 (100)
106.7 (350)
30.5 (100)
91.4 (300)
4
30.5 (100)
99.1 (325)
30.5 (100)
106.7 (350)
30.5 (100)
106.7 (350)
8
30.5 (100)
99.1 (325)
NR
30.5 (100)
106.7 (350)
240V Ratings
No Reactor
RWR at Drive
Reactor at Motor
0.37 to 4.0 kW
(0.5 to 5 Hp)
2 through 8 kHz
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
160.0 (525)
182.9 (600)
NR
NR
160.0 (525)
182.9 (600)
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives