Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 126

126
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Appendix A Motor Cable Length Restrictions Tables
Table 55 - 1336 PLUS II/IMPACT Drives, 600V – Meters (Feet)
Drive
Frame
Drive kW
(Hp)
Motor kW
(Hp)
No External Devices
(1)
(1) Values shown are for nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz.
with 1204-TFB2 Terminator
with 1204-TFA1 Terminator
(3)
(3) A 3% reactor reduces motor and cable stress but can cause a degradation of motor waveform quality. Reactors must have a turn-turn insulation rating of 2100V or higher.
Motor (NR = not recommended)
Motor (NR = not recommended)
Motor (NR = not recommended)
Motor
A
B
1329R/L
(2)
(2) When used on 600V systems, 1329R/L motors have a corona inception voltage rating of approximately 1850V.
A
B
1329R/L
A
B
1329R/L
A
B
1329R/L
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
A4
0.75 (1)
0.75 (1)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
Not
Recommended
0.37 (0.5)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
1.5 (2)
1.5 (2)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
1.2 (1.5)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
0.75 (1)
NR
NR
182.9 (600)
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
0.37 (0.5)
NR
NR
182.9 (600)
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
2.2 (3)
2.2 (3)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
1.5 (2)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
0.75 (1)
NR
NR
182.9 (600)
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
0.37 (0.5)
NR
NR
182.9 (600)
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
3.7 (5)
3.7 (5)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
2.2 (3)
NR
NR
NA
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
1.5 (2)
NR
NR
182.9 (600)
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
0.75 (1)
NR
NR
182.9 (600)
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
0.37 (0.5)
NR
NR
182.9 (600)
NR
182.9
(600)
335.3 (1100)
NR
61.0
(200)
182.9 (600)
5.5-15
(7.5-20)
5.5-15
(7.5-20)
NR
9.1
(30)
182.9 (600)
91.4
(300)
182.9
(600)
182.9 (600)
NR
61.0
(200)
182.9 (600)
30.5
(100)
91.4
(300)
182.9 (600)
C
18.5-45
(25-60)
18.5-45
(25-60)
NR
9.1
(30)
182.9 (600)
91.4
(300)
182.9
(600)
182.9 (600)
NR
61.0
(200)
182.9 (600)
30.5
(100)
91.4
(300)
182.9 (600)
D
56-93
(75-125)
56-93
(75-125)
NR
9.1
(30)
182.9 (600)
91.4
(300)
182.9
(600)
182.9 (600)
NR
61.0
(200)
182.9 (600)
61.0
(200)
91.4
(300)
182.9 (600)
E
112-224
(150-X300)
112-224
(150-X300)
NR
9.1
(30)
182.9 (600)
91.4
(300)
182.9
(600)
182.9 (600)
NR
61.0
(200)
182.9 (600)
182.9
(600)
182.9
(600)
182.9 (600)
F
261-298
(350-400)
261-298
(350-400)
NR
9.1
(30)
182.9 (600)
91.4
(300)
182.9
(600)
182.9 (600)
NR
61.0
(200)
182.9 (600)
182.9
(600)
182.9
(600)
182.9 (600)
G
224-448
(300-600)
224-448
(300-600)
NR
9.1
(30)
182.9 (600)
91.4
(300)
182.9
(600)
182.9 (600)
NR
61.0
(200)
182.9 (600)
182.9
(600)
182.9
(600)
182.9 (600)
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives