Remote I/O and Data Highway Plus (DH+)

The maximum cable length depends on the baud rate.

All three connections (blue, shield, and clear) must be connected at each node.

Serial (RS-232 and RS-485)

Follow these recommended standard practices for serial communications wiring:

One twisted pair and one signal common for RS-232.

Two twisted pair, with each pair individually shielded, for RS-485.

IMPORTANT

Only Allen-Bradley catalog number 1770-CD shielded twinaxial cabling is
tested and approved for remote I/O and DH+ installations.

Baud Rate

Maximum Cable Length

57.6 Kbps

3048 m (10,000 ft)

115.2 Kbps

1524 m (5000 ft)

230.4 Kbps

762 m (2500 ft)

IMPORTANT

Do not connect in a star topology. Only two cables can be connected at any
wiring point. Use either series or daisy chain topology at all points.