Remote i/o and data highway plus (dh+), Serial (rs-232 and rs-485) – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 24
24
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 1 Wire/Cable Types
Remote I/O and Data Highway Plus (DH+)
The maximum cable length depends on the baud rate.
All three connections (blue, shield, and clear) must be connected at each node.
Serial (RS-232 and RS-485)
Follow these recommended standard practices for serial communications wiring:
•
One twisted pair and one signal common for RS-232.
•
Two twisted pair, with each pair individually shielded, for RS-485.
IMPORTANT
Only Allen-Bradley catalog number 1770-CD shielded twinaxial cabling is
tested and approved for remote I/O and DH+ installations.
Baud Rate
Maximum Cable Length
57.6 Kbps
3048 m (10,000 ft)
115.2 Kbps
1524 m (5000 ft)
230.4 Kbps
762 m (2500 ft)
IMPORTANT
Do not connect in a star topology. Only two cables can be connected at any
wiring point. Use either series or daisy chain topology at all points.
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives