105
Motor Cable Length Restrictions Tables Appendix A
12
(1)
450
2
18.3
(60)
68.6
(225)
99.1
(325)
167.6
(550)
36.6
(120)
68.6
(225)
304.8
(1000)
365.8
(1200)
228.6
(750)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3RB400-B
40
●
500
2
12.2
(40)
68.6
(225)
99.1
(325)
167.6
(550)
36.6
(120)
68.6
(225)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R500-B
40
●
560
2
12.2
(40)
68.6
(225)
99.1
(325)
167.6
(550)
36.6
(120)
68.6
(225)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R500-B
20
525
(5)
13
630
(2)
2
12.2
(40)
61.0
(200)
99.1
(325)
167.6
(550)
36.6
(120)
61.0
(200)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R600-B
20
710
2
12.2
(40)
61.0
(200)
99.1
(325)
167.6
(550)
36.6
(120)
61.0
(200)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R750-B
20
800
2
12.2
(40)
61.0
(200)
99.1
(325)
167.6
(550)
36.6
(120)
61.0
(200)
304.8
(1000)
365.8
(1200)
198.1
(650)
274.3
(900)
365.8
(1200)
365.8
(1200)
2 x
1321-3R750-B
20
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
(3) Resistor specification is based on two cables per phase.
(4) Resistor specification is based on three cables per phase.
(5) Resistor specification is based on four cables per phase.
Table 42 - PowerFlex 700S Drives, 400V Shielded/Unshielded Cable – Meters (Feet) (continued)
Drive
No Solution
Reactor Only
Reactor and Damping Resistor
or 1321-RWR
Reactor/RWR
(see
page 129
)
Resistor
Available Options
Frame kW
kHz 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No.
Ohms
Watts
TF
A1
TF
B
2
RW
R2
RW
C
Table 43 - PowerFlex 700S Drives, 480V Shielded/Unshielded Cable – Meters (Feet)
Drive
No Solution
Reactor Only
Reactor and Damping Resistor
or 1321-RWR
Reactor/RWR
(see
)
Resistor
Available Options
Frame Hp
kHz
1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No.
Ohms
Watts
TF
A1
TF
B2
RW
R2
RW
C
1
1
2/4
7.6
(25)
12.2
(40)
83.8
(275)
83.8
(275)
7.6
(25)
91.4
(300)
152.4
(500)
152.4
(500)
152.4
(500)
152.4
(500)
152.4
(500)
152.4
(500)
●
●
●
2
2/4
7.6
(25)
12.2
(40)
83.8
(275)
83.8
(275)
7.6
(25)
91.4
(300)
182.9
(600)
182.9
(600)
152.4
(500)
182.9
(600)
182.9
(600)
182.9
(600)
●
●
●
●
3
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
91.4
(300)
182.9
(600)
182.9
(600)
152.4
(500)
182.9
(600)
182.9
(600)
182.9
(600)
●
●
●
●
5
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
91.4
(300)
243.8
(800)
243.8
(800)
152.4
(500)
243.8
(800)
243.8
(800)
243.8
(800)
1321-RWR8-DP
●
●
●
●
7.5
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
91.4
(300)
304.8
(1000)
304.8
(1000)
152.4
(500)
304.8
(1000)
304.8
(1000)
304.8
(1000)
1321-RWR12-DP
●
●
10
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
91.4
(300)
365.8
(1200)
365.8
(1200)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR18-DP
●
●
15
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
91.4
(300)
365.8
(1200)
365.8
(1200)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR25-DP
●
2
20
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
91.4
(300)
365.8
(1200)
365.8
(1200)
182.9
(600)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR25-DP
●
25
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
76.2
(250)
365.8
(1200)
365.8
(1200)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR35-DP
●
3
30
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
76.2
(250)
365.8
(1200)
365.8
(1200)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR45-DP
●
40
2/4
7.6
(25)
12.2
(40)
106.7
(350)
152.4
(500)
7.6
(25)
76.2
(250)
365.8
(1200)
365.8
(1200)
121.9
(400)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR55-DP
●
50
2/4
12.2
(40)
18.3
(60)
106.7
(350)
152.4
(500)
12.2
(40)
61.0
(200)
304.8
(1000)
365.8
(1200)
121.9
(400)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR80-DP
●
4
60
2/4
12.2
(40)
18.3
(60)
91.4
(300)
152.4
(500)
12.2
(40)
61.0
(200)
304.8
(1000)
365.8
(1200)
91.4
(300)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR80-DP
●
5
75
2/4
12.2
(40)
18.3
(60)
91.4
(300)
152.4
(500)
12.2
(40)
61.0
(200)
274.3
(900)
365.8
(1200)
91.4
(300)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR100-DP
●
100
2/4
12.2
(40)
24.4
(80)
91.4
(300)
137.2
(450)
12.2
(40)
61.0
(200)
243.8
(800)
365.8
(1200)
91.4
(300)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR130-DP
●
continued
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives