Noise related grounds – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 51
![background image](/manuals/581243/51/background.png)
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
51
Grounding Chapter 3
Figure 15 - Cabinet Grounding with a TN-S Five-wire System
Noise Related Grounds
Use appropriate grounding schemes to reduce noise when installing PWM AC
drives to reduce output that can produce high frequency common mode
(coupled from output to ground) noise currents. These noise currents can cause
sensitive equipment to malfunction if they are allowed to propagate.
L1
L2
L3
PEN or N
PE
R
S
T
R
S
T
PE PE
PE
Input Transformer
System Cabinet
AC Drive
Single-
Phase
Device
Cabinet Ground Bus
X
0
R
S
T
U
V
W
PE
A
B
C
PE
C
lg-m
C
lg-c
V
ng
Input Transformer
AC Drive
Path for Common
Mode Current
Motor Frame
Motor
Feedback
Device
Path for Common
Mode Current
Path for Common
Mode Current
Path for Common
Mode Current
Path for Common
Mode Current
System Ground
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives