Motor Cable Length Restrictions Tables Appendix A
1305 Drives
This section lists motor cable data for 1305 drives.
Table 56 - 1305 Drives, 480V, No External Devices at Motor – Meters (Feet)
Table 57 - 1305 Drive, 480V with Devices at Motor – Meters (Feet)
Drive Hp
(480V)
Motor Hp
(480V)
(480V) Using a Motor with Insulation V
P-P
Type A
Type B
1329R/L
Any Cable
Any Cable
Shielded Cable
Unshielded Cable
Maximum Carrier Frequency
4 kHz
4 kHz
2 kHz
2 kHz
High-line Derate Multiplier
0.85
0.85
0.55
0.55
5
5
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
3
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
2
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
1
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
0.5
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
3
3
9.1 (30)
30.5 (100)
91.4 (300)
121.9 (400)
2
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
1
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
0.5
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
2
2
9.1 (30)
30.5 (100)
76.2 (250)
121.9 (400)
1
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
0.5
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
1
1
9.1 (30)
30.5 (100)
68.6 (225)
121.9 (400)
0.5
9.1 (30)
30.5 (100)
121.9 (400)
121.9 (400)
0.5
0.5
9.1 (30)
30.5 (100)
45.7 (150)
106.7 (350)
Drive Hp
(460V)
Motor Hp
(460V)
Reactor at the Drive
(1)
(1) IMPORTANT: A 3% reactor reduces motor stress but can cause a degradation of motor waveform quality. Reactors must have a turn-to-turn insulating rating of 2100V or higher. Reactors are
not recommended for lightly loaded applications because over voltage trips can result at low output frequencies.
With 1204-TFB2 Terminator
With 1204-TFA1 Terminator
Using a Motor with Insulation V
P-P
Using a Motor with Insulation VP-P
(NR = not recommended)
Using a Motor with Insulation VP-P
(NR = not recommended)
Type A
Type B or 1329R/L
Type A or Type B
Type A
Type B
Any Cable
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
Maximum Carrier Frequency
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
High-line Derating Multiplier
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
5
5
15.2 (50)
182.9 (600)
182.9 (600)
NR
NR
91.4 (300)
61.0 (200)
91.4 (300)
121.9 (400)
3
15.2 (50)
182.9 (600)
182.9 (600)
91.4 (300)
121.9 (400)
99.1 (325)
61.0 (200)
152.4 (500)
121.9 (400)
2
15.2 (50)
182.9 (600)
182.9 (600)
121.9 (400)
182.9 (600)
99.1 (325)
61.0 (200)
182.9 (600)
121.9 (400)
1
15.2 (50)
182.9 (600)
182.9 (600)
121.9 (400)
182.9 (600)
99.1 (325)
61.0 (200)
182.9 (600)
121.9 (400)
0.5
15.2 (50)
182.9 (600)
182.9 (600)
182.9 (600)
182.9 (600)
99.1 (325)
61.0 (200)
182.9 (600)
121.9 (400)
3
3
15.2 (50)
91.4 (300)
182.9 (600)
NR
NR
91.4 (300)
61.0 (200)
91.4 (300)
121.9 (400)
2
15.2 (50)
182.9 (600)
182.9 (600)
91.4 (300)
121.9 (400)
99.1 (325)
61.0 (200)
152.4 (500)
121.9 (400)
1
15.2 (50)
182.9 (600)
182.9 (600)
91.4 (300)
182.9 (600)
99.1 (325)
61.0 (200)
182.9 (600)
121.9 (400)
0.5
15.2 (50)
182.9 (600)
182.9 (600)
121.9 (400)
182.9 (600)
99.1 (325)
61.0 (200)
182.9 (600)
121.9 (400)
2
2
15.2 (50)
76.2 (250)
167.6 (550)
NR
NR
91.4 (300)
61.0 (200)
91.4 (300)
121.9 (400)
1
15.2 (50)
182.9 (600)
182.9 (600)
61.0 (200)
61.0 (200)
99.1 (325)
61.0 (200)
121.9 (400)
121.9 (400)
0.5
15.2 (50)
182.9 (600)
182.9 (600)
91.4 (300)
121.9 (400)
99.1 (325)
61.0 (200)
152.4 (500)
121.9 (400)
1
1
15.2 (50)
68.6 (225)
152.4 (500)
NR
NR
45.7 (150)
61.0 (200)
45.7 (150)
76.2 (250)
0.5
15.2 (50)
182.9 (600)
182.9 (600)
NR
NR
76.2 (250)
61.0 (200)
76.2 (250)
121.9 (400)
0.5
0.5
15.2 (50)
45.7 (150)
106.7 (350)
NR
NR
NR
NR
NR
NR
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives