Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 42

42
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
1336 PLUS,
PLUS II
IMPACT
FORCE
B025
480
18.5 (25)
550
3R35-B
0.8
35
B030
480
22 (30)
600
3R45-B
0.7
45
B040
480
30 (40)
750
3R55-B
0.5
55
B050
480
37 (50)
800
3R80-B
0.4
80
B060
480
45 (60)
900
3R80-B
0.4
80
B075
480
56 (75)
1000
3R100-B
0.3
100
B100
480
75 (100)
1000
3R130-B
0.2
130
B125
480
93 (125)
1400
3R160-B
0.15
160
B150
480
112 (150)
1500
3R200-B
0.11
N200
B200
480
149 (200)
2000
3RB250-B
0.09
250
B250
480
187 (250)
2500
3RB320-B
0.075
320
B300
480
224 (300)
3000
3RB400-B
0.06
400
B350
480
261 (350)
3500
3R500-B
0.05
500
B400
480
298 (400)
4000
3R500-B
0.05
500
B450
480
336 (450)
4500
3R600-B
0.04
600
B500
480
373 (500)
5000
3R600-B
0.04
600
B600
480
448 (600)
5000
3R750-B
0.029
750
B700
480
(700)
5000
3R850-B
0.027
850
B800
480
(800)
5000
3R1000-B
0.022
1000
BP/BPR250
480
187 (250)
N/A
N/A
N/A
N/A
BP/BPR300
480
224 (300)
N/A
N/A
N/A
N/A
BP/BPR350
480
261 (350)
N/A
N/A
N/A
N/A
BP/BPR400
480
298 (400)
N/A
N/A
N/A
N/A
BP/BPR450
480
336 (450)
N/A
N/A
N/A
N/A
BX040
480
30 (40)
N/A
N/A
N/A
N/A
BX060
480
45 (60)
N/A
N/A
N/A
N/A
BX150
480
112 (150)
N/A
N/A
N/A
N/A
BX250
480
187 (250)
N/A
N/A
N/A
N/A
CWF10
600
0.75 (1)
25
3R4-C
9
4
CWF20
600
1.5 (2)
50
3R4-C
9
4
CWF30
600
2.2 (3)
75
3R8-C
5
8
CWF50
600
3.7 (5)
100
3R8-B
3
8
CWF75
600
5.5 (7.5)
200
3R8-B
3
8
CWF100
600
7.5 (10)
200
3R12-B
2.5
12
CWF150
600
11 (15)
300
3R18-B
1.5
18
CWF200
600
15 (20)
350
3R25-B
1.2
25
C015
600
11 (15)
300
3R18-B
1.5
18
C020
600
15 (20)
350
3R25-B
1.2
25
C025
600
18.5 (25)
500
3R25-B
1.2
25
C030
600
22 (30)
600
3R35-B
0.8
35
C040
600
30 (40)
700
3R45-B
0.7
45
C050
600
37 (50)
850
3R55-B
0.5
55
C060
600
45 (60)
900
3R80-B
0.4
80
C075
600
56 (75)
950
3R80-B
0.4
80
C100
600
75 (100)
1200
3R100-B
0.3
100
C125
600
93 (125)
1400
3R130-B
0.2
130
C150
600
112 (150)
1500
3R160-B
0.15
160
C200
600
149 (200)
2200
3R200-B
0.11
200
continued
Table 13 - AC Line Impedance Recommendations for Bulletin 1336 Drives (Continued)
Drive
Drive Catalog
Number
(1)
Volts
kW (Hp)
Max Supply
kVA
(2)(3)
3% Line Reactor
Open Style, 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
(4)
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives