Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 115

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
115
Motor Cable Length Restrictions Tables Appendix A
6
10
2
24.4
(80)
121.9
(400)
24.4
(80)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR12-EP
●
4
24.4
(80)
121.9
(400)
24.4
(80)
106.7
(350)
365.8
(1200)
365.8
(1200)
15
2
24.4
(80)
121.9
(400)
36.6
(120)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR18-EP
●
4
24.4
(80)
121.9
(400)
36.6
(120)
106.7
(350)
365.8
(1200)
365.8
(1200)
20
2
24.4
(80)
121.9
(400)
36.6
(120)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR25-EP
●
4
24.4
(80)
121.9
(400)
36.6
(120)
106.7
(350)
365.8
(1200)
365.8
(1200)
25
2
24.4
(80)
121.9
(400)
45.7
(150)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR35-EP
●
4
24.4
(80)
121.9
(400)
45.7
(150)
106.7
(350)
365.8
(1200)
365.8
(1200)
30
2
24.4
(80)
121.9
(400)
45.7
(150)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR35-EP
●
4
24.4
(80)
121.9
(400)
45.7
(150)
106.7
(350)
365.8
(1200)
365.8
(1200)
40
2
24.4
(80)
137.2
(450)
45.7
(150)
365.8
(1200)
304.8
(1000)
365.8
(1200)
1321-RWR45-EP
●
4
24.4
(80)
106.7
(350)
45.7
(150)
106.7
(350)
304.8
(1000)
365.8
(1200)
50
2
24.4
(80)
137.2
(450)
45.7
(150)
304.8
(1000)
304.8
(1000)
365.8
(1200)
1321-RWR55-EP
●
4
24.4
(80)
106.7
(350)
45.7
(150)
91.4
(300)
304.8
(1000)
365.8
(1200)
60
2
24.4
(80)
137.2
(450)
45.7
(150)
304.8
(1000)
304.8
(1000)
365.8
(1200)
1321-RWR80-EP
●
4
24.4
(80)
106.7
(350)
45.7
(150)
91.4
(300)
304.8
(1000)
365.8
(1200)
75
2
24.4
(80)
137.2
(450)
45.7
(150)
274.3
(900)
243.8
(800)
365.8
(1200)
1321-RWR80-EP
●
4
24.4
(80)
106.7
(350)
45.7
(150)
91.4
(300)
243.8
(800)
365.8
(1200)
100
2
24.4
(80)
137.2
(450)
45.7
(150)
243.8
(800)
243.8
(800)
365.8
(1200)
1321-RWR100-EP
●
4
24.4
(80)
106.7
(350)
45.7
(150)
91.4
(300)
243.8
(800)
365.8
(1200)
125
2
24.4
(80)
137.2
(450)
61.0
(200)
243.8
(800)
198.1
(650)
365.8
(1200)
1321-RWR130-EP
●
4
24.4
(80)
106.7
(350)
61.0
(200)
121.9
(400)
152.4
(500)
274.3
(900)
150
2
24.4
(80)
137.2
(450)
61.0
(200)
243.8
(800)
198.1
(650)
365.8
(1200)
1321-RWR160-EP
●
4
24.4
(80)
106.7
(350)
61.0
(200)
121.9
(400)
152.4
(500)
274.3
(900)
continued
Table 48 - PowerFlex 753 and 755 Wall Mount Drives, 600V Shielded/Unshielded Cable – Meters (Feet) (continued)
Drive
Rating
No Solution
Reactor Only
Reactor and Damping
Resistor or 1321-RWR
Reactor/RWR
(see
page 129
)
Resistor
Available Options
Frame
HP
kHz
1488V
1850V
1488V
1850V
1488V
1850V
Cat. No.
Ohms
Watts
TFA1
TFB2
RWR2
RWC
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives