Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

33

Power Distribution Chapter 2

Table 8 - AC Line Impedance Recommendations for PowerFlex 400 Drives

Drive

Drive Catalog
Number

(1)

(1) Shaded rows identify drive ratings without built-in inductors.

Volts

kW (Hp)

Max Supply
kVA

(2)

(2) Maximum suggested KVA supply without consideration for additional inductance.

3% Line Reactor
Open Style 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

PowerFlex
400

22CB012

240

2.2 (3.0)

50

3R12-A

N/A

N/A

22CB017

240

3.7 (5.0)

50

3R18-A

N/A

N/A

22CB024

240

5.5 (7.5)

200

3R25-A

0.5

25

22CB033

240

7.7 (10.0)

275

3R35-A

0.4

35

22CB049

240

11 (15.0)

350

3R45-A

0.3

45

22CB065

240

15 (20.0)

425

3R55-A

0.25

55

22CB075

240

18.5 (25.0) 550

3R80-A

0.2

80

22CB090

240

22 (30.0)

600

3R100-A

0.15

100

22CB120

240

30 (40.0)

750

3R130-A

0.1

130

22CB145

240

37 (50.0)

800

3R160-A

0.075

160

22CD6P0

480

2.2 (3.0)

N/A

N/A

N/A

N/A

22CD010

480

3.7 (5.0)

N/A

N/A

N/A

N/A

22CD012

480

5.5 (7.5)

N/A

N/A

N/A

N/A

22CD017

480

7.5 (10)

N/A

N/A

N/A

N/A

22CD022

480

11 (15)

N/A

N/A

N/A

N/A

22CD030

480

15 (20)

N/A

N/A

N/A

N/A

22CD038

480

18.5 (25)

N/A

N/A

N/A

N/A

22CD045

480

22 (30)

N/A

N/A

N/A

N/A

22CD060

480

30 (40)

N/A

N/A

N/A

N/A

22CD072

480

37 (50)

N/A

N/A

N/A

N/A

22CD088

480

45 (60)

N/A

N/A

N/A

N/A

22CD105

480

55 (75)

N/A

N/A

N/A

N/A

22CD142

480

75 (100)

N/A

N/A

N/A

N/A

22CD170

480

90 (125)

N/A

N/A

N/A

N/A

22CD208

480

110 (150)

N/A

N/A

N/A

N/A