Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 39
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
39
Power Distribution Chapter 2
PowerFlex
753/755
For
PowerFlex
753,
replace 20G
with 20F.
20G_D5P0
480
2.2 (3)
500
3R4-B
6.5
4
20G_D8P0
480
4.0 (5)
500
3R8-B
3
8
20G_D011
480
5.5 (7.5)
750
3R12-B
2.5
12
20G_D014
480
7.5 (10)
750
3R18-B
1.5
18
20G_D022
480
11 (15)
750
3R25-B
1.2
25
20G_D027
480
15 (20)
750
3R35-B
0.8
35
20G_D034
480
18.5 (25)
1000
3R35-B
0.8
35
20G_D040
480
22 (30)
1000
3R45-B
0.7
45
20G_D052
480
30 (40)
1000
3R55-B
0.5
55
20G_D065
480
37 (50)
1000
3R80-B
0.4
80
20G_D077
480
45 (60)
1000
3R80-B
0.4
80
20G_D096
480
55 (75)
1000
3R100-B
0.3
100
20G_D125
480
75 (100)
1000
3R130-B
0.2
130
20G_D140
480
75 (100)
1000
3R160-B
0.15
160
20G_D156
480
90 (125)
1500
3R160-B
0.15
160
20G_D186
480
110 (150)
1500
3R200-B
0.11
200
20G_D248
480
150 (200)
2000
3RB320-B
0.075
320
20G_D302
480
187(250)
2500
3RB320-B
0.075
320
20G_D361
480
224 (300)
2500
3RB400-B
0.06
400
20G_D415
480
260 (350)
3000
3R500-B
0.05
500
20G_D430
480
260 (350)
3500
3R500-B
0.05
500
20G_D485
480
298 (400)
3500
3R600-B
0.04
600
20G_D545
480
336(450)
4000
3R600-B
0.04
600
20G_D617
480
373 (500)
4500
3R750-B
0.029
750
20G_D710
480
448 (600)
4500
3R750-B
0.029
750
20G_D740
480
485 (650)
4500
3R750-B
0.029
750
20G_D800
480
522 (700)
5000
3R850-B
0.027
850
20G_D960
480
597 (800)
5000
3R1000-B
0.022
1000
20G_D1K0
480
671 (900)
5000
3R1000-B
0.022
1000
20G_D1K2
480
746 (1000) 5000
2 x 3R750-B
0.015
1500
20G_D1K3
480
821 (1100) 5000
2 x 3R750-B
0.015
1500
20G_D1K4
480
933 (1250) 5000
2 x 3R850-B
0.014
1700
20G_D1K5
480
1007(1350) 5000
2 x 3R850-B
0.014
1700
20G_D2K0
480
1082 (1750) 5000
2 x 3R1000-B
0.011
2000
20G_E1P7
600
0.75 (1)
250
3R2-B
20
2
20G_E2P7
600
1.5 (2)
500
3R4-B
6.5
4
20G_E3P9
600
2.2 (3)
500
3R4-B
6.5
4
20G_E6P1
600
4.0 (5)
500
3R8-B
3
8
20G_E9P0
600
5.5 (7.5)
750
3R8-B
3
8
20G_E011
600
7.5 (10)
750
3R12-B
2.5
12
20G_E017
600
11 (15)
750
3R25-B
1.2
25
20G_E018
600
15 (15)
750
3R25-B
1.2
25
20G_E022
600
15 (20)
750
3R25-B
1.2
25
20G_E023
600
18.5 (25)
1000
3R35-B
0.8
35
20G_E024
600
18.5 (25)
1000
3R35-B
0.8
35
20G_E027
600
18.5 (25)
1000
3R35-B
0.8
35
20G_E028
600
18.5 (25)
1000
3R35-B
0.8
35
20G_E032
600
22 (30)
1000
3R35-B
0.8
35
continued
Table 12 - AC Line Impedance Recommendations for PowerFlex 753/755 Drives (Continued)
Drive
Drive Catalog
Number
Volts
kW (Hp)
Max Supply
KVA
(1)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives