Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 36
36
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
PowerFlex
70
20AE031
600
22 (30)
1000
3R35-B
0.8
35
20AE042
600
30 (40)
1000
3R45-B
0.7
45
20AE051
600
37 (50)
1000
3R55-B
0.5
55
(1) Shaded rows identify drive ratings without built-in inductors.
(2) Maximum suggested KVA supply without consideration for additional inductance.
(3) N/A = not available at time of printing.
Table 11 - AC Line Impedance Recommendations for PowerFlex 700/700S Drives
Drive
Drive Catalog
Number
Volts
kW (Hp)
Max Supply
KVA
(1)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
700/700S
For
PowerFlex
700S,
replace 20B
with 20D.
20BB2P2
240
0.37 (0.5)
100
3R2-D
6
2
20BB4P2
240
0.75 (1)
125
3R4-A
3
4
20BB6P8
240
1.5 (2)
200
3R8-A
1.5
8
20BB9P6
240
2.2 (3)
300
3R12-A
1.25
12
20BB015
240
3.7 (5)
400
3R18-A
0.8
18
20BB022
240
5.5 (7.5)
500
3R25-A
0.5
25
20BB028
240
7.5 (10)
750
3R35-A
0.4
35
20BB042
240
11 (15)
1000
3R45-A
0.3
45
20BB052
240
15 (20)
1000
3R80-A
0.2
80
20BB070
240
18.5 (25)
1000
3R80-A
0.2
80
20BB080
240
22 (30)
1000
3R100-A
0.15
100
20BB104
240
30 (40)
1000
3R130-A
0.1
130
20BB130
240
37 (50)
1000
3R130-A
0.1
130
20BB154
240
45 (60)
1000
3R160-A
0.075
160
20BB192
240
55 (75)
1000
3R200-A
0.055
200
20BB260
240
75 (100)
1000
3R320-A
0.04
320
20BC1P3
400
0.37 (5)
250
3R2-B
20
2
20BC2P1
400
0.75 (1)
250
3R2-B
20
2
20BC3P5
400
1.5(2)
500
3R4-B
6.5
4
20BC5P0
400
2.2 (3)
500
3R4-B
6.5
4
20BC8P7
400
4 (5)
500
3R8-B
3
8
20BC011
400
5.5 (7.5)
750
3R12-B
2.5
12
20BC015
400
7.5 (10)
1000
3R18-B
1.5
18
20BC022
400
11 (15)
1000
3R25-B
1.2
25
20BC030
400
15 (20)
1000
3R35-B
0.8
35
20BC037
400
18.5(25)
1000
3R45-B
0.7
45
20BC043
400
22 (30)
1000
3R45-B
0.7
45
20BC056
400
30 (40)
1000
3R55-B
0.5
55
20BC072
400
37 (50)
1000
3R80-B
0.4
80
20BC085
400
45 (60)
1000
3R130-B
0.2
130
20BC105
400
55 (75)
1000
3R130-B
0.2
130
20BC125
400
55 (75)
1000
3R130-B
0.2
130
20BC140
400
75 (100)
1000
3R160-B
0.15
160
20BC170
400
90 (125)
1500
3R200-B
0.11
200
20BC205
400
110 (150)
1500
3R200-B
0.11
200
20BC260
400
132 (175)
2000
3RB320-B
0.075
320
continued
Table 10 - AC Line Impedance Recommendations for PowerFlex 70 Drives (Continued)
Drive
Drive Catalog
Number
(1)
Volts
kW (Hp)
Max Supply
kVA
(2)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
(3)
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives