beautypg.com

Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 36

background image

36

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

Chapter 2 Power Distribution

PowerFlex
70

20AE031

600

22 (30)

1000

3R35-B

0.8

35

20AE042

600

30 (40)

1000

3R45-B

0.7

45

20AE051

600

37 (50)

1000

3R55-B

0.5

55

(1) Shaded rows identify drive ratings without built-in inductors.
(2) Maximum suggested KVA supply without consideration for additional inductance.
(3) N/A = not available at time of printing.

Table 11 - AC Line Impedance Recommendations for PowerFlex 700/700S Drives

Drive

Drive Catalog
Number

Volts

kW (Hp)

Max Supply
KVA

(1)

3% Line Reactor
Open Style 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

PowerFlex
700/700S

For
PowerFlex
700S,
replace 20B
with 20D.

20BB2P2

240

0.37 (0.5)

100

3R2-D

6

2

20BB4P2

240

0.75 (1)

125

3R4-A

3

4

20BB6P8

240

1.5 (2)

200

3R8-A

1.5

8

20BB9P6

240

2.2 (3)

300

3R12-A

1.25

12

20BB015

240

3.7 (5)

400

3R18-A

0.8

18

20BB022

240

5.5 (7.5)

500

3R25-A

0.5

25

20BB028

240

7.5 (10)

750

3R35-A

0.4

35

20BB042

240

11 (15)

1000

3R45-A

0.3

45

20BB052

240

15 (20)

1000

3R80-A

0.2

80

20BB070

240

18.5 (25)

1000

3R80-A

0.2

80

20BB080

240

22 (30)

1000

3R100-A

0.15

100

20BB104

240

30 (40)

1000

3R130-A

0.1

130

20BB130

240

37 (50)

1000

3R130-A

0.1

130

20BB154

240

45 (60)

1000

3R160-A

0.075

160

20BB192

240

55 (75)

1000

3R200-A

0.055

200

20BB260

240

75 (100)

1000

3R320-A

0.04

320

20BC1P3

400

0.37 (5)

250

3R2-B

20

2

20BC2P1

400

0.75 (1)

250

3R2-B

20

2

20BC3P5

400

1.5(2)

500

3R4-B

6.5

4

20BC5P0

400

2.2 (3)

500

3R4-B

6.5

4

20BC8P7

400

4 (5)

500

3R8-B

3

8

20BC011

400

5.5 (7.5)

750

3R12-B

2.5

12

20BC015

400

7.5 (10)

1000

3R18-B

1.5

18

20BC022

400

11 (15)

1000

3R25-B

1.2

25

20BC030

400

15 (20)

1000

3R35-B

0.8

35

20BC037

400

18.5(25)

1000

3R45-B

0.7

45

20BC043

400

22 (30)

1000

3R45-B

0.7

45

20BC056

400

30 (40)

1000

3R55-B

0.5

55

20BC072

400

37 (50)

1000

3R80-B

0.4

80

20BC085

400

45 (60)

1000

3R130-B

0.2

130

20BC105

400

55 (75)

1000

3R130-B

0.2

130

20BC125

400

55 (75)

1000

3R130-B

0.2

130

20BC140

400

75 (100)

1000

3R160-B

0.15

160

20BC170

400

90 (125)

1500

3R200-B

0.11

200

20BC205

400

110 (150)

1500

3R200-B

0.11

200

20BC260

400

132 (175)

2000

3RB320-B

0.075

320

continued

Table 10 - AC Line Impedance Recommendations for PowerFlex 70 Drives (Continued)

Drive

Drive Catalog
Number

(1)

Volts

kW (Hp)

Max Supply
kVA

(2)

3% Line Reactor
Open Style 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

(3)