Page 76 AutoMax ControlNet Module

Publication number DSMBCN-UM001B-EN-P February 2003

Converting from Major Revision 1 to 2

If you have a network configuration in RSNetWorx that contains a
Reliance MBCN (major revision 1) and want to convert that device to a
Reliance MBCN (major revision 2), perform the following steps:

If you have access to the Reliance MBCN hardware

1. Flash upgrade the Reliance MBCN (major revision 1) to a Reliance

MBCN (major revision 2).

2. Open RSNetWorx for ControlNet.

3. Select File > New.

4. Select Network > Online.

Tip: Be sure that the Browse the network once option is disabled (select
View > Preferences) when going online.

5. Select Network > Download.

6. Select Network > Browse.

7. Select the Edits Enabled checkbox.

8. In the network configuration, select the Reliance MBCN (major

revision 2) and then select Device > Scanlist Configuration. Notice
that the status columns are now displayed; each status addresses is
131072.

9. Set the status addresses to the desired value.

10. Select File > Save.

11. Close the Scanlist Configuration Tool.

12. Select Device > Scanlist Configuration again.

13. Verify that the status addresses displayed in the Status address

column are correct.

Tip: If any status offset values are displayed incorrectly, double-click a
connection and enter the correct value.

14. Select File > Save.

If you have an offline configuration file (*.xc)

1. Open RSNetWorx for ControlNet.

2. Open the offline configuration file (*.xc) containing a Reliance

MBCN (major revision 1).

3. Select the Edits Enabled checkbox.

4. In the network configuration, select the Reliance MBCN (major

revision 1), and then select Device > Properties.

5. In the Major revision field, change to 2.