beautypg.com

Configuring scheduled data with a plc-5 – Rockwell Automation AutoMax ControlNet Communication Interface Module User Manual

Page 28

background image

Page 28 AutoMax ControlNet Module

Publication number DSMBCN-UM001B-EN-P February 2003

3. Set

the

Requested Packet Interval to the desired update rate. The RPI

must be greater than or equal to the network update time (NUT).

4. Set the input size to the number of words of data you want to receive

from the destination MBCN.

5. RSNetWorx assigns the Input Address, Output Address and Status

Address automatically if Enable automatic addressing on insert is
turned on. If you want to manually assign the addresses, enter the
values.

6. Click OK to accept the settings you have entered.

RSNetWorx automatically creates a matching Produce Data target on the
destination MBCN.

Configuring Scheduled Data with a PLC-5

Produced Data on the PLC-5, Consumed on the MBCN

In the Scanlist Configuration for the MBCN:

1. Right click on the PLC-5 from which the MBCN is obtaining data

and select Insert Connection. If necessary, switch to Edit Mode.
The Connection Properties dialog opens.

2. Set

the

Connection Name to Receive Data From.

3. RSNetWorx automatically assigns the Consume Buffer ID. If the

automatic value is incorrect, change it to the correct value.

4. Set

the

Requested Packet Interval to the desired update rate. The RPI

must be greater than or equal to the network update time (NUT).

5. Set

the

Input Size to the number of words of data you wish the

PLC-5 to produce.

6. RSNetWorx assigns the Input Address, Output Address and Status

Address automatically if Enable automatic addressing on insert is
turned on. If you want to manually assign these addresses, enter the
values.

7. Click OK to accept the settings.

RSNetWorx automatically creates a matching produce target in the
PLC-5. Start the Scanlist Configuration tool for the PLC-5 and confirm
that this is so.

Produced Data on the MBCN, Consumed on the PLC-5

1. In the main RSNetWorx window, right click on the PLC-5 and select

Scanlist Configuration. The Scanlist Configuration tool for the
PLC-5 opens.

2. Right click on the MBCN from which you want the PLC-5 to obtain

scheduled data and select Insert Connection.