Channel State

The Channel State register (9247) shows the state of each channel LED
on the MBCN. Bits 0 to 2 show the status of channel A. Bits 3 to 5 show
the status of channel B.

For detailed information, refer to the ControlNet Specification, part 10,
section 240, table 10-224.

“Railroad” indicates the 2 LEDs are flashing alternately, like a railroad
signal.

Bits

Description

2,1,0

Channel A LED state

0=off

1=solid green

2=flashing green-off

3=flashing red-off

4=flashing red-green

5=railroad red-off

6=railroad red-green

7=solid red

5,4,3

Channel B LED state, same as channel A

6

Redundancy warning, When warning, the non-active
channel in a redundant configuration is unusable by the
controller. 0 = no warning, 1 = warning

7

Active channel, Indicates which of the two channels the
receiver is currently listening to. 0 = channel B, 1 =
channel A